EQUIPMENT:
FIRE
CLASS
PRECEPT EN13
PUBLICATION:
FIRECLASS PREC EN13 INST
ISSUE No. & DATE:
2 22/07/2021
PAGE 29 of 32
Battery Specification
Panel
Repeater (AC powered)
2/4 zone
8 zone
16 zone
2, 4, 8 & 16 zone
Battery charger output:
[Temperature
compensated float
charger]
28.0V
±
0.1V@-5
°
C
26.9 V
±
0.1V@ +40
°
C.
1.5A
3A
3A
1.5A
Maximum internal
resistance of battery &
charger circuit:
(Ri max)
1
Ω
0.6
Ω
0.6
Ω
1
Ω
Battery type:
POWERSONIC
[Warning: Replace only
with identical battery]
2 off
PS12120
[12V 12Ah]
2 off
PS12120
[12V 12Ah]
2 off
PS12120
[12V 12Ah]
2 off
PS1230
[12V 3.4Ah]
Battery size (mm):
L
HT
H
W
L = 151
W = 98
H = 94
HT = 100
L = 151
W = 98
H = 94
HT = 100
L = 151
W = 98
H = 94
HT = 100
L = 133
W = 67
H = 60
HT = 66
Battery circuit protection:
[Warning: Replace only
with identical type &
rating of fuse]
F2AL250V
20mm fast blow
glass fuse
F5AL250V
20mm fast blow
glass fuse
F5AL250V
20mm fast blow
glass fuse
F2AL250V
20mm fast blow
glass fuse
Mains failed fault battery
current:
55mA
65mA
85mA
40mA
Mains failed alarm battery
current:
90mA
100mA
120mA
75mA
Environmental
Specification
All Panels & repeaters
Operating temperature:
-5ºC to 40ºC
Operating humidity: