background image

EQUIPMENT:

   

FIRE

CLASS 

PRECEPT EN13

 

PUBLICATION:

  

FIRECLASS PREC EN13 INST

 

ISSUE No. & DATE:

 

2     22/07/2021

 

PAGE 18 of 32 

11.7.4  Fire and Fault Routing Outputs 

1.  Remove the resistor from the Fire Routing 

output circuit terminals and connect the field 

wiring to the terminals, observing correct 

polarity. Check that any fault indications clear 

after a few seconds. 

2.  To operate the output, initiate a fire condition on 

a zone. Check that the fire signal is received at 

the receiving station. Silence and reset the fire 

alarm panel to clear the output. 

3.  Remove the resistor from the Fault Routing 

output circuit terminals and connect the field 

wiring to the terminals, observing correct 

polarity. Check that any fault indications clear 

after a few seconds. 

4.  Initiate a fault condition on the fire alarm panel to 

signal a fault to the remote receiving station. 

5.  Confirm the receipt of the fault warning at the 

receiving station. 

6.  Open-circuit the output wiring of each circuit in 

turn, Confirm the fire alarm panel indicates Fire 

Routing and Fault Routing faults appropriately. 

7.  Reconnect the cabling and confirm the faults 

clear. 

11.7.5  Fire Protection control signal 

1.  Ensure any fire protection equipment to be 

controlled via the Fire Protection output is locked 

off/safe before attempting any connection, 

testing or commissioning. 

2.  Remove the resistor from the Fire Protection 

output circuit terminal and connect the field 

wiring to the terminals, observing correct 

polarity. Check that any fault indications clear 

after a few seconds. 

3.  Initiate a fire condition on a zone to operate the 

output. Check that the fire signal operates the 

interface relay adjacent the fire protection 

equipment. 

4.  Open-circuit the field wiring and confirm that the 

fire alarm panel indicates Fire Protection output 

fault. 

5.  Reconnect the cabling and confirm the faults 

clear. 

6.  Final testing and commissioning of the loop 

through to the fire protection equipment, 

including test [simulated] activation of the 

equipment, should be carried out at the 

appropriate time in conjunction with the engineer 

responsible for the fire protection system. 

11.7.6  Ancillary inputs 

Remote Silence Alarms, Reset and Evacuate inputs 

should each be tested by the activation of the 

remote equipment. The response should be verified 

for each signal. 

11.7.7  Ancillary outputs 

The correct operation of equipment connected to 

the Zone Outputs, Disablement Active, Evacuate 

Active and Buzzer Active outputs should be verified 

in turn by initiating a fire condition on each of the 

appropriate zones; disabling/enabling a zone; 

operating the Evacuate button on the panel’s 

display. 

11.7.8  Repeaters 

1.  Power-up the Panel and then the Repeaters. 

Only the “Power Supply On” LEDs should be 

illuminated on the Panel and Repeaters. 

2.  At Repeater 1, turn the Access control switch to 

“1”, and press the “Evacuate” button. Check that 

the alarms operate and the internal buzzer 

operates on all repeaters. 

3.  Press the “Silence” button on the fire alarm 

panel. Check that the alarm circuits silence and 

the internal buzzer silences on all repeaters. 

4.  Repeat steps 2 and 3 for each repeater. 
5.  Operate a Manual Call Point on zone 1 and 

check for correct fire indication at each repeater. 

6.  Press the “Silence Alarms” button on a repeater 

and check that the alarms are silenced and the 

Zone 1 fire LED is constantly illuminated on all 

repeater panels. 

7.  Press the “Reset” button on a repeater and 

check that the panel and repeaters return to the 

quiescent state. 

8.  Repeat steps 5  to  7  for each zone and ensure 

“Silence Alarms” and “Reset” operate correctly 

from each repeater. 

9.  Set the DIL switches on  the C1631 Repeater 

Interface card in the fire alarm panel OFF (No 

Repeaters). Check that all repeaters indicate a 

“Comms. Fault”. 

10. Set the C1631 Repeater Interface card DIL 

switches in the fire alarm panel back to their 

previous settings and check that the repeaters 

return to normal. 

11. Set the first repeater address to 0. Check that 

the panel indicates a “Repeater fault” and any 

additional repeaters display a steady “Comms 

fault” LED. 

12. Set the first repeater address back to normal 

and check that the panel and repeaters return to 

normal. 

13. Repeat steps 11 and 12 for any other connected 

repeaters. 

 

Summary of Contents for Precept EN13

Page 1: ...UIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 1 of 32 Precept EN13 Fire Detection Alarm Panel Precept EN Repeater Installation Commissioning Manua...

Page 2: ...RY DEFAULT CONFIGURATION FOR ZONES OUTPUTS 22 14 4 ENGINEER S ZONE OUTPUT CONFIGURATION TIME OUT WARNING 22 14 5 INVALID CONFIGURATION CONDITIONS 22 14 6 LIST OF CONFIGURATION DIL SWITCHES AND THEIR F...

Page 3: ...this manual fully before commencing installation The following supporting documentation is also available FIRECLASS Precept EN13 Sales Literature FIRECLASS Precept EN13 Panel Application Guide FIRECLA...

Page 4: ...3 2 1 ZONE CIRCUITS RST SIL EVAC CLASS CHANGE BUZ ACTIVE P A B REPEATER AUX D C 0V OUTPUTS INPUTS EVAC FAULT GND O ZONE OUTPUTS 4 3 2 1 24V 0V 2 1 3 01 05 12 ISSUE 0 CEL C1717 ALARM 4 3 2 1 CIRCUITS...

Page 5: ...ACKBOX N L M a in s F u s e R ep la ce Sa m e Ty pe W ith RATING LABEL EARTH POST EARTH BAR MAINS TERMINAL ASSEMBLY RELAY BOARD Fu se In pu t Se ria l N o Pa rt N o Pr od uc t St an da rd s A pp ro va...

Page 6: ...EQUIPMENT FIRECLASS PRECEPT EN13 PUBLICATION FIRECLASS PREC EN13 INST ISSUE No DATE 2 22 07 2021 PAGE 6 of 32 Figure 4 8 16 Zone Precept EN13 panel General Assembly with optional clock module...

Page 7: ...iagram Connect to Aux DC 24V 24Vdc relay Typical zonal output wiring Field relay spec Coil resistance 2 6k to 4 5k Ohms Voltage 24Vdc Nom min 18V max 30V Fitted with suppression diode as shown Relay f...

Page 8: ...les from Panel motherboard Each Alarm circuit from the panel motherboard is connected to the IN terminals on the Alarm Relay Board Each Alarm Circuit is wired out to the sounders from the OUT terminal...

Page 9: ...le on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B GND Reset N C Inputs SIL Silence alarms EVAC Evacuate RST Reset Outputs DIS Disablement acti...

Page 10: ...Terminals Power Supply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Alarm Circuits Ma...

Page 11: ...tion resistance is greater than or equal to 1 the Batt Charge fault LED is illuminated and the Fault Output is operated The circuitry also protects against reversed connection of the batteries 9 2 Vis...

Page 12: ...eat care when lifting and transporting batteries For weights above 24 kilos lifting aids should be used DANGER Do NOT attempt to remove the battery lid or tamper with the internal workings of the batt...

Page 13: ...n an area that is clean dry and dust free where they will not be damaged You can place them inside the original packing box but you must ensure that sufficient soft packing is used to keep the door an...

Page 14: ...y 26 Connect the blue battery lead between the positive red terminal of the left hand battery and the negative black terminal of the right hand battery Note that the batteries will not power the panel...

Page 15: ...should be checked for correct audibility as specified in BS5839 1 using the Evacuate function 2 Detection zones should be commissioned next The purpose is to establish the correct functioning of each...

Page 16: ...ise the mains and check the voltage and polarity are correct before replacing the panel fuse 4 The panel will power up and enter the power up cable check mode flashing System Fault LED After about 60...

Page 17: ...nearest the panel operate each manual call point and detection device on the zone in turn o After operation of each device confirm The fire indication is provided on the panel on the correct zone The...

Page 18: ...ed out at the appropriate time in conjunction with the engineer responsible for the fire protection system 11 7 6 Ancillary inputs Remote Silence Alarms Reset and Evacuate inputs should each be tested...

Page 19: ...isabled Fault Routing Fault Disabled Yellow Flashes for a fault on the Fault Routing Output Steady when Fault Routing Output is disabled POWER SUPPLY ON FIRE FIRE ROUTING ACTIVE GENERAL FAULT POWER SU...

Page 20: ...ked and if silence before reset is configured sounders are silenced Silence Buzzer 1 Press to stop the buzzer sounding in fire or fault conditions Always available 2 In 2 Stage Delay Mode with stage 1...

Page 21: ...and the panel buzzer will silence A pulsing indication cursor will appear either on the Zone 1 Fault Disabled LED or the Sounder Fault Disabled LED Test depending upon which configuration DIL switch i...

Page 22: ...e o The panel buzzer will sound o The Cursor indication will clear o Configuration will be inhibited To clear the invalid condition check the configuration switches SW1 4 to SW1 8 on the motherboard a...

Page 23: ...1 minute within the range 0 9 minutes See Table 1 Motherboard Delay Switch Settings Table 1 Motherboard Delay Switch Settings Delay Duration SW2 2 SW2 3 SW2 4 SW2 5 NONE Off Off Off Off 1 minute On Of...

Page 24: ...14 8 Configuring the Fire Routing Fire Protection and Fault routing O Ps To configure the Fire Routing Output to volt free relay contacts remove links J10 J11 and J12 These links are combined in a sin...

Page 25: ...to 59 Press SELECT ON Time Set display HH MM SS ON Time SS flashing Press ENABLE or DISABLE to change SS to desired value 00 to 59 To set Day Night Mode Off Time Press SELECT to access day night OFF...

Page 26: ...or EEPROM1 EEPROM 0 ERROR or EEPROM 1 ERROR Note Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4...

Page 27: ...15 4 C1651 Clock Module PCB Features Figure 10 llustrates the PCB features referred to elsewhere in the documentation Figure 10 C1651 Clock Module PCB LK1 Select Operating Mode LK1 S1 WP ZERO 1 2 ON D...

Page 28: ...Voltage 230Vac 10 15 Cable requirements Minimum of 1mm2 copper protected by a 5A fuse Power Supply Output Specification Panel Repeater AC powered 2 4 zone 8 zone 16 zone 2 4 8 16 zone Maximum Short T...

Page 29: ...off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS12120 12V 12Ah 2 off PS1230 12V 3 4Ah Battery size mm L HT H W L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 151 W 98 H 94 HT 100 L 133 W 67 H 60...

Page 30: ...characteristics Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durabil...

Page 31: ...5 EN BSEN 54 4 Power supply equipment for fire detection and fire alarm systems for buildings List of essential characteristics Performance under fire conditions Pass Operational reliability Pass Dura...

Page 32: ...2 07 2021 2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice Tyco Fire Security...

Reviews: