background image

28

Application, Installation & Commissioning  Doc. version 2

4.2 Circuit Select Cursor

FIRECLASS Prescient III

2

Press the 

SELECT 

button to move the cursor to the 

required circuit fault/disabled LED. The cursor will 
move in sequence through the relevant circuits and 
will then return to the 

DOORMELDING BRAND

 fault 

LED.

3

Press 

INSCHAKELEN 

to return a circuit to normal 

operation, press 

UITSCHAKELEN

 to disable a circuit, 

press 

TEST

 to place a circuit into Test mode.

4

Repeat steps 2 & 3 for any additional circuits.

5

Press 

SELECTEER AAN/UIT

 to switch off the cur-

sor (the cursor is automatically switched off if no but-
tons are pressed for 60 seconds).

4.2.2

Configure I.S. Zones

To configure circuits to I.S. operation the required circuit 
is selected by moving the Circuit Select Cursor and then 
pressing 

INSCHAKELEN (I.S.)

 or 

UITSCHAKELEN 

(Normal) as required. The process is as follows:

1

Move the 

CONFIG I.S. INPUTS DIL

 switch on 

the control board to the ON position. The 

CONFIG 

ON LED

 on the control board will illuminate, the 

buzzer will sound, the 

SYSTEEM STORING LED

 will 

illuminate and the 

SELECTEER AAN/UIT LED

 will 

pulse. The fault/disabled LEDs for any circuits 
already set to I.S. mode will illuminate.

2

Press the 

SELECTEER AAN/UIT

 button. The Select 

Cursor will appear on the 

GROEP 1

 fault LED and the 

buzzer will silence

3

Press the 

SELECT

 button to move the cursor to the 

required circuit fault/disabled LED. The cursor will 
move in sequence through the relevant circuits and 
will then return to the GROEP 1 fault LED.

4

Press the 

INSCHAKELEN 

or 

UITSCHAKELEN

 button 

as required (to 

ENABLE I.S.

 or 

DISABLE I.S.

).

5

Repeat steps 3 & 4 for any additional circuits.

6

Press 

SELECTEER AAN/UIT

 to switch off the cur-

sor (the cursor is automatically switched off if no but-
tons are pressed for 60 seconds).

7

Move the 

CONFIG I.S. INPUTS DIL 

switch on 

the control board to the OFF position.

4.2.3

Configure SLU (Status Lamp 
Units)

If SLUs are used with the panel, the panel needs to 
know the type of SLU connected and the address of the 
SLU. The configuration process is as follows:

1

Move the 

CONFIG SLU DIL

 switch on the control 

board to the ON position. The 

CONFIG ON LED

 on 

the control board will illuminate, the buzzer will 
sound, the 

SYSTEEM STORING LED

 will illuminate 

and the 

SELECTEER AAN/UIT LED

 will pulse. The 

two-digit display for 

BLUSVERTRAGING

 will show 

SLU address 1 for the first digit and the type code of 
that SLU on the second digit:

10

 = SLU address 1, set to Type code 0 (no SLU 

with address 1)

11

 = SLU address 1, set to Type code 1

12

 = SLU address 1, set to Type code 2

13

 = SLU address 1, set to Type code 3

14

 = SLU address 1, set to Type code 4

2

Press the 

SELECTEER AAN/UIT

 button. The first 

digit will pulse (SLU address) and the buzzer will 
silence, indicating that the SLU edit mode is active.

3

Press the 

SELECT

 button to change the SLU 

address value. The second digit will show the Type 
code set for the selected address. The SLU address 
digit will change in sequence: 

1 2 3 4 5 6 7

 

and then back to 

1

.

4

When the first digit displays the address of the SLU 
to be configured, press the 

INSCHAKELEN

 button. 

The SLU address digit will go steady and the Type 
Code digit will flash.

5

Press the 

SELECT 

button to change the Type Code 

to the desired value, valid values: 

0

 

1 2 3 4

. The 

configuration is stored immediately in EEPROM.

6

Press 

INSCHAKELEN

 to switch between flashing 

the first & second digits (address change or type 
code change).

Note

Any circuits in Disabled or Test modes are 
cleared to the normal mode after power to 
the panel is lost.

Note

The I.S. configuration status is stored in 
EEPROM and is not lost when power to the 
panel is lost.

WARNING

The use of capacitors on intrinsically 
safe zones is dangerous and carries a 
risk of explosion. I.S. zones require a 
3.9 kΩ EOL resistor.

Note

If a SLU is configured to use the panel circuits 
for switch monitoring, the SLU will automati-
cally be configured as an indication only unit. 
The panel must therefore be configured for a 
type 1 SLU at the corresponding address.

Summary of Contents for Prescient III

Page 1: ...Application Installation Commissioning 120 515 161_FC P PRESCIENT3 I NL Doc version 2 24 February 2014 Conventional Fire Detection Gas Extinguishing Control Panel FIRECLASS Prescient III...

Page 2: ...re reserved in particular but not limited to the rights of copying distribution and translation No portion of this documentation including the online help may be reproduced edited copied or distribute...

Page 3: ...3 9 5 Extinguishing Isolation Valve Status ISO VALVE 16 3 9 6 Gas Released Pressure Switch GAS REL 16 3 9 7 Emergency Hold HOLD 16 3 9 8 Emergency Abort Input ABORT 17 3 10 Relay Contacts 17 3 10 1 F...

Page 4: ...RING UIT MANUAL RELEASE FAULT DISABLED 25 3 18 15 BLUSSING UIT EXTINGUISHING DISABLED 25 3 18 16 DOORM BLUSSING STORING UIT GAS RELEASED SIGNAL DISABLED 25 3 18 17 ALGEMENE STURINGEN SHUTDOWN OUTPUTS...

Page 5: ...ility 36 6 Panel Installation Commissioning 43 6 1 Cable Recommendations 44 6 2 Installation Procedure 44 6 3 Commissioning Procedure 45 7 System Maintenance 49 7 1 Overview 49 7 2 Weekly Test Routine...

Page 6: ...6 Application Installation Commissioning Doc version 2 Contents FIRECLASS Prescient III...

Page 7: ...guide is aimed at technicians who have to install a FIRECLASS Prescient III Fire detection system They should already have been given training Keyword Symbol Explanation DANGER Warning Imminent dange...

Page 8: ...device 5 k Separate monitoring of the status of non electrical disable device s Isolation valve 6 n Input from auto manual selector switches 7 o Transmission of a triggering signal to equipment withi...

Page 9: ...Sound alarms Silence Alarms Reset 10 Fully Monitored Outputs Configurable for Volt Free operation for First Stage Shutdown Second Stage Shutdown Third Stage Shutdown Auxiliary Fire Signal Auxiliary F...

Page 10: ...STORING LAGE DRUK GASCILLINDERS HOGE DRUK VERZAMELLEIDING AFSLUITER ONJUIST AFSLUITER DICHT HANDACTIVERING STORING UIT BLUSSING UIT DOORM BLUSSING STORING UIT ALGEMENE STURINGEN UIT BLUSVER TRAGING SI...

Page 11: ...on Status Input Isolation Valve Status 10K Abnormal 2K2 Open 680R Closed Status Input Gas Low 10K EOL 680R Gas Low DIL SW configurable for Normally closed operation Status Input Gas Released Pressure...

Page 12: ...uiescent 0V when activated Actuator Circuit 1 1 2V in quiescent 24V when activated 3 8V in quiescent 0V when activated Extinguishing Sounder Circuit 1 2V in quiescent 24V when activated 3 8V in quiesc...

Page 13: ...ntact Rated 1 Amp 24VDC Operating de energising on any fault including Valve Abnormal but not Valve Closed Operating on Gas P S active I P or Actuator operated when in No Discharge P S mode Open colle...

Page 14: ...et 2 A Manual Release Call Point is mounted on the door of the panel and is monitored by a separate circuit for open short circuit faults The connection for the call point is on the rear of the displa...

Page 15: ...used 24 V DC 2 AUX 1 A 24 V 0 V This output is rated at 1 A elec tronically fused 24 V DC 3 8 Status Lamp Unit The panel communicates with the Status Lamp Units SLU via two wire RS485 serial data The...

Page 16: ...1 Valve Closed Activated by a 680 resistor flashing the Valve Closed LED on the display board pulsing the internal buzzer 2 Valve Open Activated by a 2 2 resistor no indication is given on the panel...

Page 17: ...board In the Volt free mode clean contacts for Pole Normally Open Normally Closed are available rated at 1 A 30 V DC 3 10 2 Second Stage Shutdown 2ND STAGE The Second Stage Shutdown Relay is energised...

Page 18: ...s the DOORM STORING STORING UIT LED on the display In the Volt free mode clean contacts for Pole Normally Open Normally Closed are available rated at 1 A 30 V DC 3 10 7 Auxiliary Reset RESET The Auxil...

Page 19: ...Test Mode will operate the appropriate zonal fire indicator and the general sounder circuits for four seconds Switch ON A fire alarm on any zone in Test Mode will operate the appropriate zonal fire i...

Page 20: ...l without a series end of line resistor RESET INHIBIT PERIOD Five switches allow the Extinguishing System Reset Inhibit timer to be configured from 0 to 30 minutes in 1 minute increments Any of the fi...

Page 21: ...LEDs are mounted on the control board to indicate the following faults SHUTDOWN 3 FAULT Illuminates for an open or short circuit fault on the 3rd Stage monitored Out put SHUTDOWN 2 FAULT Illuminates f...

Page 22: ...fault on the Gas Low input GAS RELEASED FLT Illuminates for any open or short cir cuit fault on the Gas Released input SLU FAULT Illuminates for a fault on any Status Lamp Unit CONFIG ON Illuminates w...

Page 23: ...ff pulsing if a fire condition is detected on the aux zone illuminating steady when the alarm is accepted by operation of the Silence Alarms button The yellow LED is normally off pulsing for an open o...

Page 24: ...Stage illuminating steady during the activated condition 2nd Stage The LED remains illuminated until the Extinguishing System is reset 3 18 5 BLUSSING AKTIEF GAS RELEASED This is a red LED that is nor...

Page 25: ...steady when the Actuators are disabled Note When the actuators are disabled the Extinguishing Sounder circuit is automatically disabled 3 18 16DOORM BLUSSING STORING UIT GAS RELEASED SIGNAL DISABLED...

Page 26: ...f the button can re enable a previously disabled cir cuit set a zone for intrinsically safe operation or move the cursor between SLU number and SLU type code digits See section 4 2 for details 3 19 9...

Page 27: ...t is selected by moving the Circuit Select Cursor and then pressing INSCHAKELEN UITSCHAKELEN or TEST as required The process is as follows 1 Press the SELECTEER AAN UIT button The Select Cursor will a...

Page 28: ...mp Units If SLUs are used with the panel the panel needs to know the type of SLU connected and the address of the SLU The configuration process is as follows 1 Move the CONFIG SLU DIL switch on the co...

Page 29: ...ounded if necessary and the fire condition can be reset by operation of the HERSTEL BRANDALARM button 4 5 2 AUTOMATIC MANUAL MODE If a fire condition is detected on either zone 1 or zone 2 while the p...

Page 30: ...y The Extinguishing System Reset Inhibit timer starts and the GEBLOKKEERD LED illuminates if config ured to a non zero value The Extinguishing Sounder circuit pulses 1 second ON 1 second OFF The Extin...

Page 31: ...failed 160 mA 20 mA to 50 mA for each zone in alarm Ancillary equipment cur rent Alarm circuit current Solenoid circuit current Mains Failed current 60 mA Ancillary equip ment current Integral charger...

Page 32: ...s to allow for deterioration of the batteries during use So the minimum battery capac ity required in this example is 1 25 x 3 83 4 79 Ah 5 2 2 Battery Replacement The useful life of the standby batte...

Page 33: ...ox Incoming Mains Cable Secured with a cable tie Internally Wired Mains Cable 5A Power Supply Unit Mounted on Chassis Earth Lead to Earth Bar Earth Wire to Chassis Ambient Temperature Charger Set volt...

Page 34: ...ed by a 5 A fuse Table 9 Mains Input Specification Panel Integrated Power Supply Output Specification Parameter Value Maximum Short Term Current Output I max b 4 8 A Maximum Continuous Current I max a...

Page 35: ...m HT 100 mm Battery circuit protection F6 15AL250V 20 mm fast blow glass fuse Mains failed fault battery current 60 mA Ancillary equipment current Mains failed alarm battery current 160 mA 20 mA to 50...

Page 36: ...Series 65 ionisation detector 32 55000 317 Series 65 Optical detector 32 55000 122 Series 65 heat detector A1R 32 55000 125 Series 65 heat detector BR 32 55000 132 Series 65 heat detector CR 32 55000...

Page 37: ...l detector with SensAlert FasTest DirtAlert Flashing LED 32 ORB OH 13001 APO Orbis multi sensor detector with SensAlert FasTest DirtAlert 32 ORB OH 13003 APO Orbis multi sensor detector with SensAlert...

Page 38: ...ET Linear Smoke Beam Detector 5 SLR E IS Photoelectric Intrinsically Safe Detector 25 DCD 1E IS Rate of Rise intrinsically Safe Detector incorporating a 60 deg fixed tempera ture element 25 YBN R 4 I...

Page 39: ...fixed temperature 32 NHD G3 4T Grade 3 fixed temperature 32 NHD G H1 4T Range 1 fixed temperature detector 32 2kH 4T Photo electric 32 2IC 4T Ionisation detector 32 RB4 Mounting base System Sensor 11...

Page 40: ...ed H600 Fixed Temperature heat detector 32 H601 Fixed Temperature heat detector 32 H602 Fixed Temperature heat detector 32 H604 Fixed Temperature heat detector 32 H900 Fixed Temperature heat detector...

Page 41: ...and heat detector IS 24 MF601EX Ionisation detector IS 24 THORN S111 I R flame detector IS 12 S112 I R flame detector IS 12 S121 I R flame detector IS 12 S131 I R flame detector IS 12 S161 I R flame...

Page 42: ...d on the use of a 22 uF capacitor as the end of line device except for intrinsically safe devices in which case the EOL is a 10 k resistor If the DIL switch option 3 9 k EOL is selected then the maxim...

Page 43: ...er systems or any other radio transmit ting equipment The operating temperature range is 5 C to 40 C maximum humidity is 95 IMPORTANT SAFETY CONSIDERATIONS FOR BATTERIES WARNING Installation Complianc...

Page 44: ...s 1 8 k brown grey red gold Reset 560 green blue brown gold Valve monitoring resistors Valve open 2 2 k red red red gold Valve closed 680 blue grey brown gold 3 off End of Line Capacitors 22 F Spare 2...

Page 45: ...sistor across the terminals of the last device for any additional monitored input or output circuits being used 16 Place the chassis in the bottom of the enclosure and Re connect the internal mains ca...

Page 46: ...opriate yellow Groep fault LED pulses The Algemeen Storing LED pulses The internal buzzer pulses The fault output operates Re connect the detector and check that the panel returns to quiescent 8 Repea...

Page 47: ...BEDIENING LED illu minates 23 Place zones 1 2 into the One Man Test mode as follows Press the SELECTEER AAN UIT button The SELECT cursor should flash on the DOORMELD ING BRAND fault LED Press the SELE...

Page 48: ...nnected to the Manual Release input The primary functions of the panel have now been tested The Panel can now be configured for the specific requirements of the site via the internal DIL switches Once...

Page 49: ...all indications operate for 5 seconds and the buzzer sounds 6 Test one hold one abort and one auto manual switch if fitted These should be on separate SLUs and should be varied each week 7 Check that...

Page 50: ...50 Application Installation Commissioning Doc version 2 7 3 Battery Replacement FIRECLASS Prescient III...

Page 51: ...yout Diagram Fig 7 Control Board Layout Diagram yco Configuration Switch 1 Configuration Switch 2 Display Ribbon Connector Microcontroller Programming Header Manufacturer s Use Only Fault Status LEDs...

Page 52: ...loded View Fig 8 Panel Exploded View 6 7 211 725 2 66 0 0 18 5 6 6 7 02817 1 187 2 1 2685 225 0 1 21752 2 5 0 18 5 6 211 725 66 6 57 225 57 66 6 57 5 6 7 6 7 5 21 66 0 1 2 3 4 5 6 7 8 386 3 7 0 18 5 6...

Page 53: ...COM Detector Bases with optional Schottky Diode Zone2 wired identically to Zone1 End Of Line Capacitor 22uF 35V IN OUT COM Detector Base with optional Schottky Diode IN OUT IN OUT Manual Call Point w...

Page 54: ...VOLT C1565 Polarity Suppression Board One per circuit Actuator Solenoid Coil Resistance 30R to6K ACT2 wired identically to ACT1 NOTE 3K9 End Of Line resistor is already fitted to the C 1565board This...

Page 55: ...may be required to accommodate monitoring resistors 680 R W Normally Open Pressure Switch 10 K W EOL 680 R W Normally Open or Normally Closed Low Pressure Switch 10 K W EOL 2K2 W Valve Open 680R W Val...

Page 56: ...as Gas Released Output 1 st Stage Shutdown Output Normally de energised 10k EOL These Outputs are Reverse polarity monitored at 5 VDC They are Active at 28 VDC Nominal Each Output can be configured i...

Page 57: ...Communication Panel Terminals Z1 Z2 AUX MR 1 2 3 4 5 OUTPUTS 24V 0V AUX 250mA A B S L U 24V 0V AUX 1A 24V IN 0V IN 24V OUT 0V OUT RS485 A IN RS485 B IN RS485 A OUT RS485 B OUT Earth Bar inside Panel...

Page 58: ...trol and delay device Environmental class A 1 flooding zone CO2 high pressure CO2 low pressure inert gas Halocarbon Provided options x Extinguishing system delay x Reception of a signal representing t...

Page 59: ...FIRECLASS Prescient III 8 5 Construction Products Regulation Application Installation Commissioning Doc version 2 59...

Page 60: ...ndustriale S Scolastica 64013 Corropoli TE Italy FireclassSales tycoint com www fireclass co uk United Kingdom FIRECLASS Hillcrest Business Park Cinder Bank Dudley West Midlands DY2 9AP United Kingdom...

Reviews: