FIRECOM
™
F900-MB-6CO
Analog Addressable
CO Sounder Base
Technology Protecting Life
®
F900-MB-6CO Analog Addressable CO Sounder Base
is designed to work in conjunction with fi re alarm panels
that support the Firecom approved analog addressable
protocol.
Protocol
Intelligent Combination CO Detector & Sounder Base
Integral Carbon Monoxide Detector
Integral 85dB Sounder
Six Year Field Replaceable Electrochemical CO Senor
End of Life Signaling System Indicator
Temporal 3 Sound for Smoke Detection
Temporal 4 Sound for CO Detection
Mounts on 4” Square or Octagonal Box
Low Power Consumption
Features
F I R E C O M I N C . C O M
Analog Addressable CO Sounder Base
F900-MB-6CO
Approvals and Listings
Underwriters Laboratories
Description
The F900- MB- 6CO Analog Addressable CO Sounder
Base is a combination carbon monoxide (CO) detec-
tor and sounder base. It is designed to be used as a
stand alone device or with the addition of Firecom F900
or F1000 Series analog addressable smoke, heat or
mult-sensor detectors. The CO Sounder Base is also
designed to allow the detector to fi t one way only, without
snagging, with a simple clock wise twist motion. For
stand alone CO detection, two blank covers are avail-
able, the F900-MB-6COBC-LP for the low profi le and
the F900-MB-6COBC-HP for the high profi le.
The CO Sounder base sounds a temporal 3 sound for
smoke detection and a temporal 4 sound for carbon
monoxide detection. The integral sounder is capable
of producing an 85db tone at 10 feet. The CO Sounder
Base is powered by a UL listed Notifi cation Appliance
Circuit, and may be synchronized with other CO Sounder
Bases using appropriate synchronization modules.
Each base has locking feature whereby a socket screw
on each detector may be turned to locate in a fi xing hole
in the base to prevent unauthorized removal.
The 6-inch diameter F900-MB-6CO Analog Addressable
CO Sounder Base mounts to 4-inch octagonal and
4-inch square boxes. When mounting on a ceiling, install
at least 4-inches from the wall. When mounting detector
on the wall, install 4 to 12 inches from the ceiling.