background image

F

IRE

F

LEX

®

  N

2

 

B

LAST

®

 

Integrated Fire Protection System 

O

WNER

'

O

PERATION 

&

 

M

AINTENANCE 

M

ANUAL

 

Page 10 of25 

FM-076B-0-6A

 

4.8.3  Main drain test 

A main drain test shall be conducted to determine 
whether there has been a change in the condition of the 
water supply piping and control valves (as per NFPA25). 

1.  Record the water supply pressure indicated by the 

pressure gauge

 (B12)

2.  FULLY OPEN the drain test valve

 (B6)

3.  Record residual water supply pressure indicated by 

the pressure gauge

 (B12)

4.  SLOWLY CLOSE the drain test valve

 (B6)

5.  Record the water supply pressure indicated by the 

pressure gauge

 (B12)

6.  Readings shall be compared with those made at the 

time of the original acceptance tests or with those 
made at the time of the last test to determine whether 
there has been any deterioration of the water supply. 

Note:

  A main drain test shall be conducted any time the 

water supply control valve (

D1

) is closed and reopened at 

the system. 

4.8.4  Monthly inspection 

1.  Gauges on preaction system shall be inspected to 

ensure that normal air and water pressures are being 
maintained. 

2.  Verify that the control valves are in the following 

condition: 

ƒ

 

In the normal open or closed position. 

ƒ

 Properly 

supervised. 

ƒ

 Accessible. 

ƒ

 

Free from external leaks. 

3.  The deluge valve (

A1

) and associated components 

shall be externally inspected to verify the following: 

ƒ

 

The valve is free from physical damage. 

ƒ

 

All trim valves are in the appropriate open or 
closed position. 

ƒ

 

The valve seat is not leaking. 

ƒ

 

Electrical components are in service.

 

4. Check 

alarm 

device

 (C1)

 switch by opening the alarm 

test valve

 (B5)

5.  Conduct low air pressure supervisory test (refer to 

chapter 4.8.1). 

6.  Refer any noted problems or deficiencies to 

authorized service personnel for correction. 

4.8.5  Semi-annual inspection 

1.  Check main water supply control valve

 (D1)

 switch 

upon movement of the hand wheel. 

2. Check 

alarm 

device

 (C1)

 switch by opening the alarm 

test valve

 (B5)

.

 

3.  Check the sprinklers piping for corrosion and 

damage. 

4.  Check all piping supports to insure they are tight and 

properly secured. 

5.  Perform functional test of all components of the 

system. 

WARNING   

Prior to any functional tests, the actuator

 (C)

 

must be removed to prevent cylinder

 (A)

 discharge. 

4.8.6 Annual inspection 

1.  Perform semi-annual inspection. 

2.  Check all detectors at the remote releasing control 

panel. 

3.  Check all releasing conditions. 

4.  Check all audible & visual devices at the remote 

releasing control panel. 

5.  Perform sequence of operation (refer to chapter 4.4). 

6.  Perform manual emergency release test of the 

preaction system. 

7.  Perform full trip test. 

8.  Perform drain test. 

4.8.7  Long term inspection 

1.  Alarm valves and their associated strainers, filters, 

and restriction orifices shall be inspected internally 
every 5 

years unless tests indicate a greater 

frequency is necessary. 

2. Riser 

check

 (D2)

 shall be inspected internally every 

5 years unless tests indicate a greater frequency is 
necessary. 

3.  Test on gauge (gauge precision required: less than 

3% of the full scale). 

4.9  MAINTENANCE 

The system shall be maintained in full operation condition 
at all times. 

All troubles or impairments shall be corrected promptly 
consistent with the hazard being protected. 

The 

N

2

 Blast

®

 

FPS

-

250 and FPS-750 utilize three 

different filters, seen in the figure to the right.  The filters 
must be changed out annually or every 1000 hours (hour 
meter located on the outside bottom right corner of the 
cabinet) of operating time, whichever comes first. 
(please refer to South-Tek manual for details) 

Summary of Contents for N2 BLAST

Page 1: ...FireFlex Preaction Double Interlocked Electric Pneumatic Release Self Contained Fire Protection Systems O M Manual FM 076B 0 6A 2020 The Leader in Nitrogen Generation Technology...

Page 2: ...al is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Page 3: ...r 3 2 5 BlastOff Leak Detection System 3 2 6 N2 Blast AutoPurge System 3 2 7 Nitrogen generator 3 Air Pressure Maintenance Device 3 3 PREACTION SYSTEM 4 3 1 DESCRIPTION 4 3 2 CONFIGURATION 4 3 3 RELEA...

Page 4: ...mpressor Style A 16 5 2 Air Pressure Maintenance Device Style B 17 5 3 OPERATION 18 5 3 1 Air supply Style A 18 5 3 2 Air supply Style B 18 5 4 MAINTENANCE AND INSPECTION 19 5 4 1 Air supply style A 1...

Page 5: ...be installed in a dry and clean location Verify that all equipments are properly heated and protected to prevent freezing and physical damage The unit and its components must be kept free of foreign...

Page 6: ...Key alike locks on all cabinet doors Manufactured under ISO 9001 quality control procedures 1 6 CONFIGURATION FIREFLEX N2 Blast Preaction systems are built around the Viking trim using straight throug...

Page 7: ...t in larger Fire Protection Systems those requiring more Nitrogen to compensate for the NFPA acceptable leak rate 2 5 BlastOff Leak Detection System Unless the leak rate is catastrophic the supervisor...

Page 8: ...1724 kPa working water pressure max and is available in the following diameters f 1 40 mm f 2 50 mm f 3 80 mm f 4 100 mm 3 3 RELEASE Release trim for the electric pneumatic operated double interlocke...

Page 9: ...If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or FIREFLEX Systems Inc 8 Make sure that building owner or a delegate...

Page 10: ...ntrol valve D1 8 When full flow develops from the drain test valve B6 CLOSE the drain test valve and verify that there is no flow from the drip check valve B7 when the plunger is pushed 9 FULLY OPEN t...

Page 11: ...S To take system out of service WARNING Placing a system out of service may eliminate the fire protection capabilities of the system Prior to proceeding notify all Authorities Having Jurisdiction Cons...

Page 12: ...l come on and the Operating green light will illuminate until the N2 storage tank pressure reaches maximum approximately 75 Psi and the compressor shuts off Reset the remote release control panel Sole...

Page 13: ...the main drain valve D3 2 Verify that low air supervisory operate within pressure setting from table 5 3 3 Close the Inspectors test valve or the main drain valve D3 4 Establish recommended air press...

Page 14: ...efer any noted problems or deficiencies to authorized service personnel for correction 4 8 5 Semi annual inspection 1 Check main water supply control valve D1 switch upon movement of the hand wheel 2...

Page 15: ...6B 0 6A Page 11 of 25 Figure 4 1 P ID Tank Provided with brackets and Strap Riser towards the nozzles N2 Blast Compressor Air Maintenance Device s AMD s Supplied by Fireflex Preaction Compressor Preac...

Page 16: ...Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL Page 12 of25 FM 076B 0 6A Figure 4 2 FIREFLEX N2 Blast shown without doors FM 06LM 0 1A 4 FM 06LM 0 1A 4 See figures 4 3 4 4 for...

Page 17: ...icted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Drain test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve PORV B10 Emergency release valve B11 Prime...

Page 18: ...076B 0 6A Figure 4 4 FIREFLEX N2 Blast storage tank FM 06LM 0 1A 1 FM 06LM 0 1A 1 N1 Nitrogen generator air pressure maintenance device N2 Nitrogen generator air pressure maintenance device control v...

Page 19: ...system refer to chapter 4 6 PLACING THE SYSTEM BACK IN SERVICE AFTER OPERATION 5 FULLY OPEN the system shut off valve D4 Reset the remote releasing control panel Figure 4 7 Shut off valve option Main...

Page 20: ...30Vac 60Hz 220Vac 50Hz 1 6 5 0 Amp 2 5 Amp 1 3 Amp 1 3 7 4 Amp 3 7 Amp 2 5 Amp 1 2 10 0 Amp 5 0 Amp 4 0 Amp 1 18 0 Amp 9 0 Amp 6 0 Amp 115 230 Vac 60Hz air compressor selection Table H P CFM 40 PSI Sy...

Page 21: ...ry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an Air Pressure Maintenance Device APMD trim factory mounted in the FIREFLEX N2 Blast cabinets E16 This se...

Page 22: ...eplace the cover on the switch E2 Note Do not turn the cut out adjustment screw middle screw all the way down in one shot Proceed by steps Use the same method turning the cut out adjustment screw COUN...

Page 23: ...e pump to run hotter and results in longer operating cycles N2 Blast Nitrogen generator Intake filters The N2 BLAST FPS 250 and FPS 750 utilize three different filters The filters must be changed out...

Page 24: ...d air flow through the APMD E5 will allow Determine the appropriate pressure to be maintained in the system refer to table 5 The APMD E5 should be checked after installation or repair and adjusted as...

Page 25: ...section replaced by Dehydrator option A when used TO OPTIONAL ACCELERATOR plugged when not used FM 061H 0 118B 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR Air option c...

Page 26: ...RATOR plugged when not used E4 plugged with SureFire trim FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TEST PORT system side E5 TO SPRINKLER RISER E8 Note The external air supply must be restricted to in...

Page 27: ...dicated on figure 6 1 6 2 REMOTE CONTROLED FIREFLEX N2 Blast Without integrated releasing control panel For application with FIREFLEX N2 Blast unit provided without integrated releasing control panel...

Page 28: ...OUTLET TBB TBA TBC CONTROL PANEL except for Remote Controlled Unit SPRINKLER RISER SCH 40 GROOVED OUTLET T R G M D P F S FM 06LM 0 2A OPTIONAL SHUT OFF VALVE CONTROL PANEL TBA TBB TBC N Q C A B Syste...

Page 29: ...RING OF INPUT POWER SOURCE Branch circuit for air compressor shall not be the same as the control panel power source 6 7 8 9 10 11 C NO NC MAIN VALVE C NO NC SHUT OFF VALVE Contact provided for connec...

Page 30: ...other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some jurisdictions may not allow limitations on how l...

Reviews: