Page 1 of 8
Integrated Fire Protection System
E
Control Section
FM-076A-0-97A
1. Self-contained unit with integrated release
control panel
1.1 Product description
The release control panel of the
T
OTAL
P
AC
®
3
system is an
add-on unit that is installed inside the cabinet at the
factory.
Once the left door is opened, the locked control panel door
can be opened to give access to the control panel, the
emergency battery compartment, and other related
equipment.
A releasing circuit disconnect switch is located at left of the
release control panel.
The control panel can be easily flipped once unlatched
from the right side, giving access to electrical junction's
box of the unit.
1.2 Self-contained unit with Viking VFR-400 release
control panel
The Viking release control panel model VFR-400 is a listed
and approved, microprocessor based fire control/releasing
panel. The battery compartment can hold two 12 volt
batteries which are charged by an internal battery charger.
Batteries are available to provide up to 90 hours of backup
power during AC power failure.
The VFR-400 panel can be used with a wide range of
compatible initiating devices such as pull stations, heat
detectors (including linear heat detectors), photo-electric
and ionization smoke detectors.
For complete compatibility list, please see the Viking
VFR-400 Installation, operation and instruction manual
provided with the
T
OTAL
P
AC
®
3
unit.
Pre-configured programs allow field programming for one
of ten possible input/output combinations that are available
and listed for use with the
T
OTAL
P
AC
®
3
system.
A field wiring electrical junction boxes is integrated with the
cabinet for connection of detection system, auxiliary
contacts and signaling devices. All supply, inputs &
outputs are factory wired from the control panel to terminal
strips (TBA, TBB & TBC) for contractor's field wiring (see
figure 4 and the section
F
ELECTRICAL
).
Gauges to indicate water supply pressure and priming
water pressure are all visible through clear Lexan windows
on the left door.
1.3 Technical Data
Cabinet
Steel enclosure: Refer to section
G
CABINET SECTION
for
further details.
Temperature: 39°F (4°C) to 120°F (48°C)
Humidity: 85% relative humidity (non-condensing) at
90°F (32°C) maximum
AC Power
Releasing control panel AC power shall be supplied by a
dedicated circuit breaker, as per NFPA 70, Section 760
and Canadian Electrical Code, Section 32.
The panel is available for use with either 120VAC, 60Hz or
220/240VAC, 50/60Hz power supply.
1.4 Visual Indicators
Red LED’s:
- Initiating device circuit active (4)
- Notification/Release circuit active (4)
- Common alarm
Green LED:
- AC power
Yellow LED’s:
- Initiating device circuit trouble (4)
- Output circuit trouble (4)
- Supervisory initiating zone (4)
- Supervisory bell output active (4)
- Supervisory 1
- Supervisory 2
- Power trouble
- Supervisory trouble
- System trouble
- Ground fault
- Discharging/Pre-Discharge
- Alarm silenced