Page 1 of 6
Integrated Fire Protection System
F
Electrical Section - Deluge System - F
IRE
C
YCLE
®
III Release
FM-076A-0-72A
1. Self-contained configurations
The Viking VFR-400 releasing control panel integrated
within the
T
OTAL
P
AC
®
3
F
IRE
C
YCLE
®
III
unit is factory wired
and programmed with the configuration selected at the
time of purchase.
All field wiring is to be wired to the contractor wiring
junction box and terminals provided (TBA, TBB & TBC).
WARNING
Only the following pre-configured programs are
Listed/Approved
with
the
actual
T
OTAL
P
AC
®
3
F
IRE
C
YCLE
®
III
U
nit. Changing for another pre-configured
program may alter the fire protection capabilities of the
system and/or void Listing/Approval and warranty. Consult
FireFlex Systems before making any change.
1.1 Releasing circuit disconnect switch
A key switch located at left of the release control panel,
allows the user to electrically disconnect the N.C. solenoid
valve for maintenance purpose. A supervisory signal and
a trouble signal are present at the release control panel.
When disabled, the
T
OTAL
P
AC
®
3
F
IRE
C
YCLE
®
III
unit
remains operational with the opening of the manual
emergency release valve, unless the main water supply
valve is closed.
1.2
F
IRE
C
YCLE
®
III
release
Program #8:
Single hazard, one N.C. alarm zone, one
manual station zone, one water flow zone and three
supervisory zones.
On activation of
DETECTION ZONE 1
(N.C. detection)
or
DETECTION ZONE 4
(manual release), the system alarm
audible devices sound and if required, can be silenced
manually. The N.C. (normally closed) solenoid valve of the
system is energized, allowing the water to escape from the
priming chamber of the deluge valve. The clapper of the
deluge valve opens, filling the outlet chamber and
sprinklers piping network with water. The
DETECTION
ZONE 3
(water flow) is activated. System water flow audible
devices and the water motor gong (if installed) will sound.
Water is discharged through all automatic sprinklers.
Note:
When
DETECTION ZONE 3
(water flow) is activated, the
alarm audible devices sound and cannot be silenced.
On activation of
SUPERVISORY ZONE 1
(supervisory),
SUPERVISORY ZONE 2
(valve tamper) or
DETECTION ZONE 2
(supervisory), supervisory audible devices will sound.
Table 1 - Program #8: Output and relay circuits activated by input circuits
PROGRAM #8
DELUGE
F
IRE
C
YCLE
®
III
RELEASE
OUTPUT CIRCUITS
(NAC)
RELAY CIRCUITS
EVENTS
1
2
3
4
T
R
O
U
B
LE
R
E
LA
Y
A
L
A
R
M
R
E
LA
Y
S
U
P
E
R
V
IS
O
R
Y
R
E
LA
Y
W
A
T
E
R
F
LO
W
R
E
LA
Y
D
E
LU
G
E
R
E
L
E
A
S
IN
G
IN
H
A
Z
A
R
D
A
L
A
R
M
B
E
L
L
S
U
P
E
R
V
IS
O
R
Y
B
E
L
L
R
E
LE
A
S
E
S
O
LE
N
O
ID
N
.O
. S
O
LE
N
O
ID
INPUT CIRCUITS
SUPERVISORY
ZONE
1
Supervisory
A
T
A
2
Valve tamper
A
T
A
DETECTION
ZONE
1
N.C. heat detectors
2
A
A
3
A
A
E
2
Supervisory
A
T
A
3
Water flow
A
A
T
A
A
4
Manual release
A
A
T
A
E
EVENTS
AC power failure
1
E
Battery failure
E
NAC open/short circuit
E
Ground fault
E
A
= Alarm activated (on short circuit)
T
= Trouble activated (on open circuit)
E
= Event actuated
(1) Trouble relay will activate 90 minutes after trouble LED and local buzzer.
(2) Alarm is activated on open circuit. Soak timer starts when
DETECTION ZONE 1
returns to normal condition.
(3) NAC 3 is deactivated when soak timer cycle is complete.