Page 3 of 8
Integrated Fire Protection System
G
Dimensional Data & Cabinet - Deluge System
FM-076A-0-108A
Figure 2 - Floor anchoring dimensions
1" (25mm)
A
FRONT
5" (127mm)
B
TOP VIEW
Ø ¾" (19mm) TYP.
Ø ¾" (19mm) TYP.
FM-061H-0-128A-2
A
FRONT
TOP VIEW
1" (25mm)
B
5" (127mm)
Table 3 - Floor anchoring dimensions
Unit size
A
B
1½
(40mm)
25"
(635mm)
15"
(380mm)
2"
(50mm)
25"
(635mm)
15"
(380mm)
3"
(80mm)
37¾"
(959mm)
15"
(380mm)
4"
(100mm)
37¾"
(959mm)
15"
(380mm)
6"
(150mm)
48"
(1220mm)
15"
(380mm)
8"
(200mm)
56"
(1422mm)
21"
(530mm)
Figure 3 - Cabinet & doors clearance detail
T
OTAL
P
AC
3
UNIT
FM-061H-0-275A-1
B min.
C min.
A min.
B min.
TYPICAL
MECHANICAL
ROOM
Figure 4 - Knockouts details
2½" Typ.
(65mm)
9"
(230mm)
High voltage
Low voltage
Combined ½ & ¾ knockouts
2½"
(65mm)
FM-061H-0-68B-12
Top of Cabinet
8½"
(215mm)
3"
(75mm)
Table 4 - Cabinet clearance dimensions
Unit size
A
B
C
1½
(40mm)
24"
(610mm)
12"
(305mm)
48"
(1219mm)
2"
(50mm)
24"
(610mm)
12"
(305mm)
48"
(1219mm)
3"
(80mm)
24"
(610mm)
12"
(305mm)
60"
(1524mm)
4"
(100mm)
24"
(610mm)
12"
(305mm)
60"
(1524mm)
6"
(150mm)
24"
(610mm)
12"
(305mm)
70"
(1778mm)
8"
(200mm)
32"
(813mm)
12"
(305mm)
78"
(1981mm)
Note :
Minimum dimensions are according to door clearance
and external piping requirements.