background image

REQUIREMENTS

1.   Only non-combustible materials should come in direct contact with any part of the Fire Pit. Underneath area should  

      be non-combustible as well.
2.   Only use ¾” gas supply line to the Fire Pit. Based on the selection of the fire pit size, the proper brass fittings should   

      be used to ensure a proper installation.
3.   Determine the size of the round or square Fire Pit you are preparing to install (Refer to page 3).
4.   You must provide a round or square cut out to place the fire pit into the non-combustible enclosure surround. Use   

      the pattern from the shipping carton for sizing.
5.   Follow the local code requirements for the gas type being used. This Fire Pit should be installed in accordance with  

      local codes and ordinances or in the absence of local codes, with the latest National Fuel Gas Code, ANSI Z223.1   

      NFPA54 or CSA B149.1, Natural and Propane Installation Code in Canada.
6.   Fire Pits create high temperatures, it is very important to have any combustibles at a safe distance. 
7.   Normal operation of the Fire Pit is with a battery box that is supplied with your system (Fig 4). The battery box has  

     12-feet of black sleeved wire that is to be passed through the junction box provided. This wire should not be cut or  

      spliced and the junction box can be placed in the facing of the vertical finish of the fire pit, if you place the wire under  

      ground you should install those wires into an approved protective conduit/sleeve material.
8.   If (optional) 120VAC adapter (Pg.13) is going to be used to power this system it is required to follow all local codes  

      or National Electrical Code ANSI/NFPA 70 for installation of this electrical outlet. A breaker on wall switch with         

      approved outdoor outlet must be used to insure safety to this Fire Pit.  When not in use the breaker should be in the  

      OFF position. 
9.   Fire pit should never be left unattended while in operation. It should always be a safe distance from all trees and     

      combustible landscape materials. 
10.  Construction of the finished fire pit should be stable and solid. From the bottom of the control box that houses the  

      gas valve and module, it should be a minimum if of 4-inches to the ground level. See figure #1. Drainage is critical to  

      ensure that water does not damage and valve components. Never install the fire ring system below grade.
11.  

CAUTION: 

A minimum of 18 square inches of cross ventilation (2 sides) is required to keep the components  

        in good working order.

  

12.  The insulation square pad provided with the Fire Pit is to be placed foil up toward the bottom of pan on top of the  

       valve box. 
13.  Never fill the cavity under and around the valve box with any material, this is a provided air space necessary for  

       ventilation. 
14.  These products are designed for outdoor use only. Not approved for any indoor use. 
15.  This Fire Pit is designed to have Lava Rock/Media completely covering the fire star burner, so that the fire star is  

        invisible. Do not cover more than 1” above the top of the covered fire star burner. When purchasing Lava Rock it  

        is recommended to use minimum of 1” diameter as a base to fill the burner pan. Decorative glass covering may  

        be loosely scattered on top of the rock if desired or non-combustible logs may be added for a campfire look. If logs  

        are chosen, do not place on decorative glass base, use only Lava Rock as the base.   

NOTE

: If using all glass  

        media, glass must be a minimum of 1/4-inch diameter or larger.
16.  Gas lines and fittings must be installed in to the non-combustible structure. All gas connections must be leak tested  

       before installation of the fire pit. Soapy water leak detection is required before regular use of the fire pit.
17.  Do not use material that will absorb moisture over time and will not release this moisture quickly. Moisture can boil  

       in this material and can rapidly break apart and cause damage or personal injury.
18.  Never leave any other combustible material on top of the fire pit. This could cause unsafe operation of this system  

       and damage to the component that will not be covered under our warranty.
19.  Cover the complete burner with lava or decorative Rock material (min. 1-inch diameter). Completely cover the   

       star burner, no more than 1 inch above the burner.

INSTALLATION OF FIRE PIT INTO AN APPROVED ENCLOSURE

REV. 10-10-12  Page 6

Summary of Contents for FPB-1414DSI/N

Page 1: ...tdoor Fire Pit Installation and Operating Instructions IF YOU CANNOT READ OR UNDERSTAND THESE INSTALLATION INSTRUCTIONS DO NOT ATTEMPT TO INSTALL OR OPERATE THIS APPLIANCE Warning For Outdoor Use Only PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE INSTALLTION PRECAUTION This fire pit requires a minimum 18 square inches of cross ventilation Failure to provide proper ventilation can void the warrant...

Page 2: ...58 6 9 95 8 8 A3 B2392 254 8 C D438E 3F 38 58 897 4 4659 958 G377 H C I 4 F234 56673589 38 58 897 4 4659 4 92 54 5 95 6 J F 8FJ 95 2 C 03 2 1 02 2 03 2 01 902 2 0 7 90 A 21 1 6 2 1 0 9 2 61 6 10 7 A 6 1 2 B 1 1 7 03 K L D M K 1L 0 1 1 2 1 03 1 4 5 6 1 7 28 27 2 03 5292 20 032 1 03 1 66 2 9 61 6 1 2 0 02 A 7B 0 0A 0 1 02 A 1529 1 2 0 9 9 9 2 B 1 1 61 6 10 7 C 7 03 2 0 02 A 6 1 02 7 2 0 9 2 01 902 0...

Page 3: ...provide a minimum of 1 2 square inches 3 23 cm for each pound of propane LP contained in the tank see example below Every opening must have minmum dimensions to allow entrance of a 1 2 3 2 mm diameter rod Ventilation openings in side walls must not connunicate directly with other enclosures of the fire pit The cyclinder valve must be easily accessible by hand Connections should be easy to leak tes...

Page 4: ...Pit 4 Cross Ventilation Requirements 4 Installation Into An Approved Enclosure Requirements 5 Installation of Battery Pack 6 Installation of Lava Rock Media 6 Learning the Remote to Module 7 Operation Initial Start Up 8 Replacement Parts 9 Replacement Parts List 10 Fire Pit Maintenance 11 Trouble Shooting 11 Wiring Diagram 12 Accessory Parts 13 Warranty 14 TABLE OF CONTENTS REV 10 10 12 Page 3 ...

Page 5: ...h Btu s Natural Propane LP Low Btu s Natural Propane LP FPB 19DSI N 80 000 Btu s 50 000 Btu s FPB 25DSI N 110 000 Btu s 50 000 Btu s FPB 1414DSI N 45 000 Btu s 30 000 Btu s FPB 2020DSI N 110 000 Btu s 50 000 Btu s FPB 2626DSI N 110 000 Btu s 50 000 Btu s Table 2 Btu Specifications NG LP Min Inlet 5 0 WC 11 0 WC Max Inlet 10 5 WC 13 0 WC Table 3 Gas Pressures MODEL FPB 19DSI N FPB 25DSI N FPB 1414D...

Page 6: ...he Fire Pit to the male flared brass fitting secured to the black iron pipe Note Flare to flare connections do not require Teflon tape or pipe sealant IMPORTANT Installation of Natural or LP gas should be done by a qualified installer service agency or gas supplier The appliance and its manual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the s...

Page 7: ...rom the bottom of the control box that houses the gas valve and module it should be a minimum if of 4 inches to the ground level See figure 1 Drainage is critical to ensure that water does not damage and valve components Never install the fire ring system below grade 11 CAUTION A minimum of 18 square inches of cross ventilation 2 sides is required to keep the components in good working order 12 Th...

Page 8: ...e burner and control system should be tested before the media lava rock is installed NOTE If using optional 120V power adapter AF 4000ADP24 you must use a switch or a breaker that can be turned ON and OFF easily Normal operations are with battery power and nothing else would have to be done INSTALLATION OF BATTERY INTO TRANSMITTER You have one handheld transmitter model RCAF 3 and you will need to...

Page 9: ...he control box See fig 9 The cover will slide down exposing the gas valve and control module 2 Find the black module attached to the inside of the control box Locate the Learn Button on the bottom of the module 3 Once the Learn button is located press and release the button once You will hear a beep indicating that the module is ready to receive a transmitter code See fig 10 4 Take the transmitter...

Page 10: ... the optional 120V power adapter you must turn the switch or breaker ON If using the standard battery pack ensure batteries are installed and the Fire Pit is ready to operate 3 Press the ON button on the handheld transmitter You will hear the ignitor probe sparking light the gas and fire pit will come on WARNING Do not stand over Fire Pit during ignition or operation due to high surface tempera tu...

Page 11: ...REV 10 10 12 Page REPLACEMENT PARTS 1 2 3 11 12 13 8 16 7 15 14 ON OFF HI LOW 17 SKYTECH SKYTECH SKYTECH SKYTECH 19 6 5 18 4 ...

Page 12: ...t shown 1 ST3 100 1030 10 DSI Valve Box Assembly not shown 1 ST2 010 1010 11 Stainless DSI Fire Pit Valve Box Only 1 ST3 100 1020 13 Stainless DSI Fire Pit Valve Box Cover Only 1 ST3 100 1021 13 Control Module AF 5000MOD 1 Inside valve box 1 ST3 030 1039 14 AF 4025 DSI Gas Valve 5 0 WC Natural Gas 1 ST2 080 1025 15 1 2 Flex Gas Line 46 inch Length 1 T 200 9898 46 16 Air Shutter Orifice NG 13 Used ...

Page 13: ... of Fault Warn users if the pilot is not successfully ignited in 15 seconds How to Clear Press OFF then ON buttons to re attempt ignition What to Check 1 Ensure gas supply is turned on 2 Ensure that the gas line is purged of air Air is common in the gas line if the appliance has just been installed has been disconnected then re connected to the gas line or if the appliance has been unused for an e...

Page 14: ... operating range 8 Make sure that there is not a large metal obstruction between the remote transmitter and the control module Igniter Electrode Sparks Frequently During Operation 1 The control module will generate a spark at the igniter electrode if the system is in the ON position but does not sense a flame 2 Make sure that the flame sensor electrode is clean Soot buildup will insulate the elect...

Page 15: ...ice air mixer for 19 20 pits using 18 inch firestar LP Conversion Kit MODEL FPB 25LPCK Brass orifice air mixer for 25 26 pits 24 inch firestar LP Conversion Kit The following accessories are available from your local firegear dealer distributor Each accessory comes with a separate installation manual Read each instruction thoroughly before installing FCC REQUIREMENTS NOTE THE MANUFACTURER IS NOT R...

Page 16: ...ranty period Travel diagnostic cost service labor to repair the defect and freight charges on warranty parts to and from the factory will be responsibility of the owner Fire Gear LLC will not be responsible for labor charges and or damage incurred in installation repair and replace ment or for incidental or consequential damages This Limited Warranty does not cover any failures or operating diffic...

Reviews: