REV. 7-22-14  Page 3

Firestar Fire Pits

If this fire pit is permanently connected to a gas piping 

system from a remote supply tank, installation must be in 

accordance with local codes or, in absence of local codes, 

with the National Fuel Gas codes ANSI Z223/1/NFPA 54.

•  If constructing an enclosure to conceal a propane 

tank/LP cyclinder- the enclosure must adhere to the 

following construction requirements:

•  Enclosures may be constructed with one side 

      compeletely OPEN or if the enclosure is built with four

      (4) sides, a top and a bottom, then as  ollows:

•  A Liquid Propane (LP) gas cyclinder enclosure re-

quires four (4) ventilation openings at the top and bot-

tom of the enclosure.  The openings must adhere to 

the minumum requirements according to the capacity 

of the cyclinder (See diagram 1).

•  Each opening in the enclosure must be equally sized 

and spaced at a minimum of 180º.  Openings must 

remain unobstructed.  

•  Top ventilation openings are required on the side walls 

of the enclosure within 5-inches (127mm) of the top 

enclosure.  They need to be of equal size, 

       unobstructive and spaced 180º apart.  The openings 

       need to be a total area of 1 in² /lb (14.2 cm²/kg) of fuel

       storage capacity.

•  Bottom opening must provide a minimum of 1/2 

square inches (3.23 cm²)  for each pound of Liquid 

Propane (LP) contained in the tank (see example 

below.

•  Every opening must have minmum dimensions to allow 

entrance of a 1/2” (3.2 mm) diameter rod.

•  Ventilation openings in side walls must not connunicate 

directly with other enclosures of the fire pit.

•  The cyclinder valve must be easily accessible by hand.  

Connections should be easy to leak test inside the 

enclosure.  A door on the enclosure is acceptable only 

if easily opened without the use of tools and is non 

       locking.

•  The enclosure needs to be isolate the cylinder from the 

burner compartment and provide protection from 

       radiation, act as a flame barrier and protect cylinder 

       from foreign material.

•  The enclosure needs to allow connection, disconnec-

tion and inspection of the connection of the Liquid 

Propane (LP) gas cylinder.

•  The enclosure should allow testing of any connetion on 

the Liquid Propane (LP) cylinder that might be 

•  distrubed during installation.

REMOTE PROPANE / LP GAS ENCLOSURES

 INSTALLATION GUIDELINES

5” Max.

5” Max.

2” Min.

1” Max.

A

C

B

Diagram 1.

Propane/LP Tank Enclosure Specifications

A - Opening 180º apart from each other
B - Min.. 2” (50.8mm) from floor/ground to base of tank
C - Max. 1” (25.4mm) from tank base to bottom of opening

ALL

 fire pits in this manual come equipped for Natural gas (NG) however,  if you are considering 

converting to Liquid Propane (LP) gas use the guidelines below for proper tank storage and ensure you 

purchase the proper orifice air shutter kit.

Summary of Contents for FPB-14SFSMT-N

Page 1: ... side of cross ventilation Failure to provide proper ventilation can void the warranty Match Throw MT Description FPB 19RFSMT N 19 Round Stainless Pan Firestar FPB 25RFSMT N 25 Round Stainless Pan Firestar FPB 14SFSMT N 14 Square Stainless Pan Firestar FPB 20SFSMT N 20 Square Stainless Pan Firestar FPB 26SFSMT N 26 Square Stainless Pan Firestar FPB 32SFSMT N 32 Square Stainless Pan Firestar FPB 38...

Page 2: ...er use this appliance in an enclosed space such as a camper tent car or home WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death FOR YOUR SAFETY Do no store or use gasoline or other flammable vapors and liquids in the vicinity of this or another appliance WARNING Improper installation adjustment al...

Page 3: ...n 4 Installation into an Approved Enclosure 5 Requirements 5 Installing Key Valve Piezo Ignitor 5 Typical Installation Drawings 6 Installing Battery in Piezo Ignitor 7 Ignitor Alignment 7 Installation of Lava Rock Media 7 Operation 8 Lighting Instructions 8 Air Shutter Adjustment 8 Replacement Parts 9 Replacement Parts List 10 Fire Pit Maintenance Trouble Shooting 11 Optional Accessories Conversio...

Page 4: ... each pound of Liquid Propane LP contained in the tank see example below Every opening must have minmum dimensions to allow entrance of a 1 2 3 2 mm diameter rod Ventilation openings in side walls must not connunicate directly with other enclosures of the fire pit The cyclinder valve must be easily accessible by hand Connections should be easy to leak test inside the enclosure A door on the enclos...

Page 5: ...FPB G29RFSMT N 2 750 30 00 31 25 29 5 8 FPB G33RFSMT N 2 750 34 00 35 25 33 5 8 Note Btu listings are based on 7 0 WC for Natural Gas and 11 0 WC for Liquid Propane LP at the burner orifice Flex line size and proper gas pipe sizing will also affect Btu s As a result your Btu s may vary slightly from Table 2 specifications Firestar Fire Pits Model Match Throw BTU H Natural Propane LP Factory Orific...

Page 6: ...essary pipe for the distance required and then install a manual shut off valve at the exterior house wall If pipe is to pass through a foundation or house wall make sure to re seal the area around the pipe with weather sealant 3 From manual valve extend gas pipe to the fire pit location NOTE If pipe is to be placed in an underground trench check with local codes for required depth and materials ne...

Page 7: ...vering may be loosely scattered on top of the rock if desired or non combustible logs may be added for a campfire look If logs are chosen do not place on decorative glass base use only lava rock as the base 10 Gas lines and fittings must be installed in to the non combustible structure All gas connections must be leak tested before installation of the fire pit Soapy water leak detection is require...

Page 8: ...a i l Fig 5 Typical installation NOTE Gas supply shut off and flex line to the key valve are not supplied Firestar Fire Pits Note A 1 x 2 black iron or galvanized coupler nipple not supplied can be used as a spacer between the manual valve and the valve flange to add additional support to hold the manual key valve in place Key Valve Flange Non Combustible Wall Material Non Combustible Wall Materia...

Page 9: ...nce 6 Temporary storage of this appliance indoors is permissible only if it has been disconnected from its fuel supply Natural or Liquid Propane LP gas line WARNING 1 This appliance is hot when operated and can cause sever burns if contacted 2 Do not burn any solid fuels in this appliance Firestar Fire Pits MATCH THROW LIGHTING INSTRUCTIONS Key Fig 7 Inserting Key into Valve O N O F F Fig 6 Key Va...

Page 10: ...REV 7 22 14 Page 9 REPLACEMENT PARTS 1 2 3 6 7 O N O F F 10 11 9 Firestar Fire Pits 8 5 4 ...

Page 11: ...S 36 4 1 x 2 Blank Cover Plate 1 ST3 100 1030 5 NPT Brass Nut 1 ST3 113 1032 6 7 8 Flat Washer Spacer 1 ST3 113 1026 7 Flex Gas Line 46 inch Length 1 T 200 9898 46 8 Air Shutter Orifice NG Used on 14 Fire Pit 1 OAS NG42 8 Air Shutter Orifice NG Used on 19 20 Fire Pits 1 OAS NG31 8 Air Shutter Orifice NG Used on 25 26 29 Fire Pits 1 OAS NG22 8 Air Shutter Orifice NG Used on 38 Fire Pit 1 OAS NG03 8...

Page 12: ...stalled during heavy use Sooting may also occur periodically on the screen of the ignitor hood To clean brush off with a dry bristle brush or cloth Keep soot away from clothing or furniture 6 Over time stainless steel parts discolor when heated usually a golden or brown hue This discoloration is normal and does not affect the performance of the appliance REV 7 22 14 Page 11 TROUBLE SHOOTING Sympto...

Page 13: ...O THIS EQUIPMENT SUCH MODIFICATIONS COULD VOID THE USER S AUTHORITY TO OPERATE THE EQUIPMENT FOR TECHNICAL SERVICE CALL 855 498 8324 Firegear Outdoors 9230 Conservation Way Fort Wayne IN 46809 For Sales 888 672 8929 WEB SITE www firegearoutdoors com REV 7 22 14 Page 12 CONVERSION KITS OPTIONAL ACCESSORIES The following accessories are available from your local Firegear dealer distributor Each acce...

Page 14: ...verify purchase date and establish warranty period Travel diagnostic cost service labor to repair the defect and freight charges on warranty parts to and from the factory will be responsibility of the owner Firegear Outdoors will not be responsible for labor charges and or damage incurred in installation repair and replacement or for incidental or consequential damages This Limited Warranty does n...

Reviews: