REV. 8-30-18 Page 7
Linear Outdoor Fire (LOF)
REQUIREMENTS
1. Only non-combustible materials should come in direct contact with any part of the Linear Outdoor Fire. Under
neath area should be non-combustible as well.
2. Only a minimum ¾” gas supply line to the Linear Outdoor Fire. Based on the selection of the Linear Outdoor Fire
size, the proper brass fittings should be used to ensure a proper installation.
3. Determine the size of the round or square Linear Outdoor Fire you are preparing to install (Refer to page 3).
4. You must provide a rectangular opening out to place the Linear Outdoor Fire into the non-combustible
enclosure surround. Do not exceed the maximum opening from Table 1, dimension B.
5. Follow the local code requirements for the gas type being used. This Linear Outdoor Fire should be installed in
accordance with local codes and ordinances or in the absence of local codes, with the latest National Fuel Gas
Code, ANSI Z223.1 NFPA54 or CSA B149.1, Natural and Propane Installation Code in Canada.
6. Linear Outdoor Fire pits create high temperatures, it is very important to have any combustibles at a safe distance
See Fig. 2 page 4).
7.
CAUTION: A minimum of 18 square inches of cross ventilation (per side) is required to keep the enclosure
dry.
8. These products are
designed for outdoor use only
. Not approved for any indoor use.
9. This Linear Outdoor Fire is designed to have Lava Rock/Media completely covering the burner tube so that the
burner is invisible. Do not cover more than 1” above the top of the burner. When purchasing Lava Rock it is recom
mended to use minimum of 1” diameter as a base to fill the burner pan. Decorative glass covering may be loosely
scattered on top of the rock if desired or non-combustible logs may be added for a campfire look. If logs are
chosen, do not place on decorative glass base, use only Lava Rock as the base.
NOTE
: If using all glass media,
glass must be a minimum of ¼” diameter or larger.
10. Gas lines and fittings must be installed in to the non-combustible structure. All gas connections must be leak tested
before installation of the Linear Outdoor Fire. Soapy water leak detection is required before regular use of the
Linear Outdoor Fire.
11. Do not use material that will absorb moisture over time and will not release this moisture quickly. Moisture can boil
in this material and can rapidly break apart and cause damage or personal injury.
12. Never leave any other combustible material on top of the Linear Outdoor Fire. This could cause unsafe operation
of this system and damage to the component that will not be covered under our warranty.
13. Cover the complete burner with lava or decorative Rock material (min. 1-inch diameter). Completely cover the
star burner, no more than 1-inch above the firestar burner.
INSTALLATION OF INTO AN APPROVED ENCLOSURE
INSTALLING KEY VALVE AND PIEZO IGNITOR
The key valve contents: 1- key valve, 1- key and 1- flange. (See figure 4). The valve requires a 1 ¼” round clearance
hole in the non-combustible enclosure wall. See the instructions supplied with the key valve for more specific details.
Note: Be sure to leak test all fitting before operation. Figure 5 shows an example of a typical installation.
After the Linear Outdoor Fire burner pan is installed run the Piezo ignitor wires into the electrical junction box. Piezo wires
are 24-inches in length; ensure your installation does not exceed the wire length for proper connection.
Primary Gas
Supply
ON
O
FF
Fig. 4
Key valve components.