10
OD42 Outdoor Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may
NOT
be recessed into combustible or non combustible
construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace be
installed only in accordance with these instructions.
MINIMUM CLEARANCES TO COMBUSTIBLES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fi replace be installed only in accordance with these instructions.
F
E
D
A
C
B
OD42 Clearance Requirements
Clearance:
Dimension
Measured From:
A: Sidewall
11" (203mm)
Side of Fireplace Opening
B: Ceiling
36" (914mm)
Top of Fireplace Opening
C: Mantel Height (min.)
18" (457mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
12" (304mm)
From Wall
E: Alcove Width
57"(1148mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required
E
F
Alcove
A
B