Fire Control Panel - Model 08451
SYSTEM ISOLATION
Rev 1.0
Page | 2
2
Isolation using the Control Panel
2.1
Isolate Function
Normal Condition
Panel Isolated
To
isolate
the control panel, press and hold Single Button until a 1 beep
and the “Isolated”
LED is illuminated.
•
Isolating disables automatic activation. Manual Activation will remain operational only
from the Control Panel
–
NOT from the remote actuators.
•
When isolated, the control panel continues to monitor for alarm and fault, and show the
alarm and fault indications, but will not operate the siren and the automatic discharge.
•
When isolated, any change in the detector status, will cause the panel sounder to
operate for 1 second as an alert of the status change, but the panel will remain isolated.
•
The isolate function will also silence the siren/strobe and the internal sounder but will not
cancel the alarm or fault indication.
2.2
Restore the panel from Isolate Mode
To restore the control panel to normal operation, press a Single Button and ensure the
“Isolated” LED turns off
.
ACTIVTION OF THE SYSTEM FROM THE PANEL REQUIRES
BOTH SWITCHES TO BE PRESSED AND HELD FOR 5 Secs.