Fire Control Panel - Model 08451 

SYSTEM ISOLATION 

Rev 1.0 

 

Page | 2  

2

 

Isolation using the Control Panel 

2.1

 

Isolate Function 

 

 

Normal Condition 

Panel Isolated 

To 

isolate

  the control panel, press and hold  Single Button until  a 1 beep 

and the  “Isolated” 

LED is illuminated.

  

 

Isolating  disables  automatic  activation.    Manual  Activation  will  remain  operational  only 
from the Control Panel 

 NOT from the remote actuators. 

 

When isolated, the control panel continues to monitor for alarm and fault, and show the 
alarm and fault indications, but will not operate the siren and the automatic discharge. 

 

When  isolated,  any  change  in  the  detector  status,  will  cause  the  panel  sounder  to 
operate for 1 second as an alert of the status change, but the panel will remain isolated. 

 

The isolate function will also silence the siren/strobe and the internal sounder but will not 
cancel the alarm or fault indication. 

2.2

 

Restore the panel from Isolate Mode 

To  restore  the  control  panel  to  normal  operation,  press  a  Single  Button  and  ensure  the 

“Isolated” LED turns off

 

ACTIVTION OF THE SYSTEM FROM THE PANEL REQUIRES 

BOTH SWITCHES TO BE PRESSED AND HELD FOR 5 Secs. 