The FP-08450 Control Panel provides several programming options, 
allowing it to be adapted to site conditions.  The 2-way DIP switches 
inside the panel next to the terminal block allow one of 4 modes to 
be selected.  To access the DIP switches, open the panel enclosure.  

Note:

 All programmed settings should be recorded in the logbook. 

Note: 

If a Discharge Delay Module (P/N FP-08850) is installed, panel 

must

 be programmed 

for extended discharge. 

7

 

Operation 

7.1

 

LED Indicators 

The FP-08450 Control Panel uses LED indicators to notify the operator 
of the condition of the control panel and each of the monitored circuits.   
If an LED is illuminated, it indicates the following: 

Circuit 

LED 

Condition 

Power 

 

Power supply is available 

Circuit 1 Alarm 

 

System is in alarm condition 

Circuit 2 Alarm 

 

System is in alarm condition 

Fault 

 

System is in fault condition and needs servcing 

Isolated 

 

System has been isolated using buttons on panel 

Discharging 

 

System has initiated activation sequence 

7.2

 

Isolate Function 

To isolate the control panel, press and hold Mode Switch 1 until a 1 beep is heard and the 

“Isolated” LED is illuminated.

 

To  restore  the  control  panel  to  normal  operation,  press  Mode  Switch  1  and  ensure  the 

“Isolated” LED turns off.

  

Isolating disables automatic activation.  Manual Activation will remain operational.

 

When isolated, the control panel continues to monitor for alarm and fault, and show the alarm 
and  fault  indications,  but  will  not  operate  the  siren  and  the  automatic  discharge.    When 
isolated,  any  change  in  the  detector  status,  will  cause  the  panel  sounder  to  operate  for  1 
second as an alert of the status change, but the panel will remain isolated.   
The  isolate  function  will  also  silence  the  siren/strobe  and  the  internal  sounder  but  will  not 
cancel the alarm or fault indication. 

Switch 1 

Mode 

Switch 2 

Mode 

 

OFF 

Standard Discharge  

Power Applied for 2 
seconds 

DEFAULT

 

 

OFF 

Manual Discharge 

Detectors operate 
siren/strobe only 

 

 

ON 

Extended Discharge 

Power applied for 240 
seconds 

 

ON 

Automatic Discharge 

Detection on Circuit 1 
Alarm will discharge 
system 

DEFAULT

 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Reviews: