background image

Page | 15  

8

 

Commissioning 

Commissioning  should  be  performed  when  the  fire  control  panel  is  not  in  an  alarm/fault 
condition.  

Note: 

No personnel should be in the risk area until the fire system is fully isolated. 

Note:

    Where  shutdown  relays  have  been  installed,  all  personnel  should  be  made  aware 

equipment will not be operable until testing is completed. 
1.

 

Isolate the control panel (see 7.2 Isolate Function) and disconnect the any installed FirePro 
aerosol generators.  This will generate a fault on the fire control panel. 

2.

 

Connect a FP-08800 Universal Test Lamp to the 

“Discharge” output

 to the panel (marked 

yellow).  Turn off the Isolate function. 

 

3.

 

Inspect  installed  FirePro  generators  to  ensure  they  are  in  good  condition,  and  that  the 
relevant stream lengths and thermal clearances are observed. 

4.

 

Test the fault monitoring system by disconnecting and reconnecting all connected detection 
devices  and  the  siren  strobe  circuit  one  at  a  time.  Ensure 

the  “Fault”  LED  indic

ator 

illuminates and the internal sounder is heard each time a circuit is disconnected. 

5.

 

Test the detection circuit(s) and ensure that any alarm condition activates the siren. 

6.

 

Manual Discharge Testing: 

 

-

 

Perform  a  manual  discharge  test  by  pressing  and  holding  both  mode  switches 
continuously for 5 seconds. 

-

 

Following the activation sequence, ensure the test lamp has operated.  

-

 

Isolate the panel to silence the alarm.  The control panel should now display a fault.   

-

 

Reset the connected test lamp by pressing the reset button on the lamp.  The control 
panel should no longer be in alarm/fault condition. 

-

 

Turn off the Isolate function. 

7.

 

Automatic Discharge Testing:  Not Allowed under Marine Regulations.  

The panel 

must not be programmed for automatic discharge, unless manual call points are installed.  
If no call points installed skip to step 7. 

Each detection device connected to “Circuit 1 Alarm” must be tested individually.

 

-

 

Perform an automatic discharge test by activating each of the manual call points. 

-

 

Following the activation sequence ensure the test lamp has operated.  

-

 

Isolate the panel to silence the alarm.  The control panel should now display a fault.   

-

 

Reset the connected test lamp by pressing the reset button on the lamp.   

-

 

Reset the control panel by pressing and holding a single mode switch until 2 beeps are 
heard.  The control panel should no longer be in alarm/fault condition. 

-

 

Turn off the Isolate function. 

8.

 

While performing discharge test, ensure operation of all installed siren/strobes.  These must 
be audible and visible at all points of the risk area. 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Reviews: