The 

control panel’s circuit arrangement provides a number of layers of electronic protection 

designed  to  minimise  the  effects  of  electromagnetic  emissions  and  prevent  accidental 
discharges of the suppression system. 
Shielded, fire rated cable (FP-09500) is required to be used throughout every installation to 
protect  the  fire  system  from  electromagnetic  emissions.    Cables  should  be  installed  with 
appropriate  clearances  from  any  cables  or  equipment  that  may  produce  high  levels  of  RF 
interference.  

13

 

Safety Data Sheet (SDS) - FirePro 

This is an EXTRACT ONLY from the full SDS.  To view the full SDS go to 

www.chemwatch.com.au

 

 
PRODUCT NAME 

CELANOVA FIREPRO 

 
 
PRODUCT USE 

Fire extinguishing agent.

 

HAZARDOUS SUBSTANCE. DANGEROUS GOODS. 

According to NOHSC Criteria, and ADG Code. 

 

POISONS SCHEDULE - 

None 

RISK 

SAFETY 

 

Contact with combustible material may cause fire. 

 

Harmful if swallowed  

 

Irritating to eyes and skin.  

 

May cause SENSITISATION by skin contact.  

 

Harmful  to  aquatic  organisms  may  cause  long-  adverse 
effects in the aquatic environment. 

 

Cumulative effects may result following exposure  

 

May produce discomfort of the respiratory. system* 

 

Possible respiratory sensitiser*. 

 

May possibly affect fertility* (limited evidence). 

 

Keep away from combustible material  

 

Avoid exposure - obtain special instructions before use. 

 

To clean the floor and all objects contaminated by this material 
use water and detergent. 

 

Keep away from food drink and animal feeding stuffs. 

 

In case of contact with eyes rinse with plenty term of water and 
contact Doctor or Poisons Information Centre.  

 

If  swallowed  IMMEDIATELY  contact  Doctor  or.  Poisons 
Information Centre (show this container or label). 

 

This material and its container must be disposed of as hazardous 
waste. 

FIRST AID MEASURES

 

SWALLOWED 

 

If swallowed do NOT induce vomiting. 

 

If vomiting occurs, lean patient forward or place on left side (head-down position, if possible) to maintain 
open airway and prevent aspiration.  Observe the patient carefully.

 

 

Never give liquid to a person showing signs of being sleepy or with reduced awareness.

 

 

Give water to rinse out mouth, then provide liquid slowly and as much as casualty can comfortably drink.

 

 

Seek medical advice.

 

EYE 

 

If this product comes in contact with the eyes: 

 

Wash out immediately with fresh running water. 

 

Ensure complete irrigation of the eye. 

 

Seek medical attention without delay; if pain persists or recurs seek medical attention. 

 

Removal of contact lenses after an eye injury should only be undertaken by skilled personnel.

 

SKIN 

 

If skin contact occurs: 

 

Immediately remove all contaminated clothing, including footwear. 

 

Flush skin and hair with running water (and soap if available). 

 

Seek medical attention in event of irritation.

 

INHALED 

 

If dust is inhaled, remove from contaminated area. 

 

Encourage patient to blow nose to ensure clear passage of breathing. 

 

If irritation or discomfort persists, seek medical attention.

 

 

 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...