background image

Page | 3  

1

 

Introduction 

1.1

 

General Information 

The FirePro FP-08450 Fire Control Panel is a combined detection and extinguishant system, 
and is compliant for use in marine (AMSA NSCV). 
The FIP (fire indicator panel) incorporates: 
-

 

2x Detection circuits; 

-

 

1x Extinguishing Discharge circuit; 

-

 

1x Siren/Strobe circuit; 

-

 

Programmable Activation (automatic and/or manual); 

-

 

Fault Monitoring system; 

-

 

Isolation Function. 

1.2

 

How Does it Work 

All 

FirePro

 Aerosol Generators use the latest generation FPC solid compound. Upon activation, 

the solid compound is transformed into a rapidly expanding, highly efficient gas, based on 
Potassium salts. It does not deplete oxygen levels.

 The built-in fail-safe activation system 

ensures operation of the generators when required, even if everything else fails.  At 300⁰C the 

FPC block changes to a potassium-based gas to extinguish the fire. 

Ozone Depletion Potential (O.D.P.) = 0 
Atmospheric Life Time (A.L.T.) = 0 

Global Warming Potential (G.W.P.) = 0 
Non-corrosive & Non-toxic 

1.3

 

In Case of Fire 

If a fire occurs, equipment operators should do the following: 
1.

 

Detection will initiate an alarm condition on the FirePro System  

2.

 

The  siren/strobe  will  operate  and  if  shutdown  relays  have  been  installed,  equipment 
shutdown will be initiated. 

3.

 

Evacuate all personnel from the risk area. 

4.

 

Close all hatches and openings, and shutdown engines and any extraction fans or vents. 

5.

 

Manual Activation:

 Press and hold both mode switches continuously for 5 seconds to 

activate the system. 

6.

 

Remote Activation Switches:

 The control panel will automatically begin the activation 

sequence when remote activation switches (where installed) are pushed (Det Circuit 1). 

7.

 

Keep the FirePro suppression gas within the risk until the fire is extinguished and not able 
to re-ignite. 

8.

 

Do not start engine or fans until the fire is extinguished.  Operating the exhaust fans will 
enable the gas to escape the risk area and could allow the fire to re-ignite. 

9.

 

Do not enter the risk until it has been rendered safe. 

10.

 

Recommended clean up after discharge is with soapy water and a cleaning agent based on 
citric acid. 

11.

 

Following a discharge, replace all installed FirePro Generators. 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Reviews: