background image

Page | 4  

2

 

Components List 

 

FP-08450  
Fire Control Panel 

Detection and extinguishant 
control system 

4x DP-3000 
1x DP-2000 
2x FP-08950 
1x  
1x  
1x 
1x 

Deutsch Plug 3 Pin F, c/w heatshrink 
Deutsch Plug 3 Pin M, c/w heatshrink 
End-of-line Plug 4k7

 (Detection) 

End-of-line Diode 1N4004 (Siren/Strobe) 
Charging Diode 1N5404 (Backup Power) 
End-of-

Line Resistor 3k3Ω

 (Discharge) 

Operator’s Manual

 

Agent Release Circuit 

Siren / Strobe Circuit 

 

FP-08918 

Wiring  loom  and  Splitter  Cable  for 
installaion  of  multiple  FirePro 
generators.

 

 

FP-08940 

Siren/Strobe

 

Discharge Circuit 

 

FirePro Aerosol 
Generator 

100g 

 500g Unit. 

Constructed from Stainless Steel. 
Comes with installed Deutsch Plug 
for easy install 

 

FP-6200 

Heavy Duty Bracket 316 SS. 
Suits FP-100, 200, 500 FirePro 
Aerosol Generators.

 

 

FirePro Aerosol 
Generator 

1200g 

 5700g Unit. 

Constructed from Stainless Steel. 
Comes with installed Deutsch Plug 
for easy install.

 

 

FP-6100 

Heavy Duty Bracket 316 SS. 
Suits FP-1200, 2000, 3000 5700 
FirePro Aerosol Generators.

 

Detection Circuit (Circuit 1 Alarm & Circuit 2 Alarm) 

 

FP-08920 

Marine  Grade  Thermal  Detector 
60°C  Fixed.    Other  temperatures 
available on request.

 

 

FP-14053 

Manual Call Point 
Internal OR External

  

 

FP-09510 

Linear Heat Detection Cable 182° C

 

 

FP-09511 

Linear Heat Detection Installation kit. 
Mounting  Clips,  2x  Junction  Boxes 
with strain relief cable glands and 1x 
EOL for monitoring.

 

Installation Components 

Service Components 

 

FP-09500 

2 Hour Fire Rated Shielded Cable.

 

 

FP-08960 

Signage for the System.  A sheet of 
different size labels.

 

 

FP-08870/8871/8872 

Power Control Module 
Provides  back  up  power  for  control 
panel.

 

 

 

FP-08800 

FirePro  Simulator 

  for  Testing  & 

Commissioning. 

 

Additional Modules 

 

FP-08850 

Discharge Delay Module 
Allows additional FirePro generators 
to be discharged

 

 

FP-08860 

Shutdown Relay Module 
Provides facility for equipment 
shutdown

 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Reviews: