background image

Page | 8  

4

 

Installation 

FirePro generators

 must

 remain disconnected until system is completed and fire control panel 

is no longer in a fault or alarm condition. The FirePro Universal Test Lamp (P/N FP-08800) can 
be used to take the panel out of a fault condition. 

Note:

 Any required extension leads 

must

 be constructed as per the instructions in 3.8 Cabling 

Requirements. 

Note:

 It is recommended that one circuit is installed and connected at a time to isolate the 

cause of any faults that may occur during installation.  The supplied End-of-line plugs and Test 
Lamp may be used to keep the control panel out of a fault condition. 
1.

 

Main Power:

 When panel has been mounted in a suitable location, connect main supply 

power using a Lead to the power input (marked red).  The recommended source for the 

main power supply input is the vessel’s emergency batteries.

 

 

2.

 

Backup Power: 

Where the ves

sel’s emergency batteries are not suitable, the control panel 

will need to be connected to a secondary power supply (see below) or the FP-08870/08871 
Power Control Module (see product manual). 

 

If  a  secondary  power  supply  is  used,  it 

must 

be  the  same  voltage  as  the  main  power 

source.  The supplied 1N5404 Charging Diode must be installed in the positive terminals of 
Main Power and Backup Power. The diode is polarised, so the positive lead of the diode 
(marked with a grey band) should be terminated in terminal 3 (+ Backup Power) and the 
negative lead terminated in terminal 1 (+ Main Power). 

 

 

 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...

Reviews: