Specifications 

General 

Dimensions 

143L x 84W x 31D mm 

Material 

ABS plastics, black colour 

Ingress Protection 

IP54 

Operating Temperature 

-40 to 85 degrees Celsius 

Fault Monitoring 

 External 

-

 

Circuit 1 Alarm 

 Open/Closed 

-

 

Circuit 2 Alarm 

 Open/Closed 

-

 

Siren/Strobe 

 Open/Closed  

-

 

Discharge 

 Open/Closed 

Fault Monitoring 

 Internal 

-

 

Poly-switch fuse operated 

-

 

Loss of internal 5V supply 

-

 

Internal microprocessor malfunction 

Power Supply Input 

Mains Operating Voltage 

12-30VDC 

Mains Operating Current 

20mA on 12V 

23mA on 24V 

Backup Power 

See FP-08870 / 08871 / 08872 manual 

Detection Output 

Circuit 1 Alarm & 
Circuit 2 Alarm

 

No. of Detection Zones 

Operating Voltage 

12-30VDC (same as main supply voltage) 

Detection End-of-line 

4k7

Ω Resistor

 

Maximum Detectors per Zone 

-

 

30 Conventional Detectors 

-

 

100m Linear Heat Detection 

-

 

30 Manual Call Points 

Alarm Threshold 

3.6V Fault sensing threshold:  0.53V 

Compatible Detectors 

Hochiki SLV-AS Smoke Detector 

Hochiki DCD-AE3M Thermal Detector 
14053 External Call Point 

09510 180˚C Linear Heat Detection

 

Discharge Output 

Discharge Output Current 

2A at 12VDC   

4A at 24VDC 

Discharge End-of-line 

3K3Ω Resistor

 

Maximum FirePro Generators 

2 in series at 12VDC 

4 in series at 24VDC 

Standard Discharge Delay 

5 seconds from automatic/manual activation 

Siren/Strobe Output 

Siren/Strobe Output Current 

Max 0.5A 

Siren/Strobe Output Protection 

0.5A poly-switch resettable fuse 

Siren/Strobe End-of-line 

1N4004 Diode 

Maximum Siren/Strobes 

Compatible Siren/Strobes 

Flashni Xenon Sounder Beacon 

Agent Released Input 

Input Type 

Thermal Switch, NC, Latching, Non-resettable 

Operation 

Thermal Event >80˚C

 

 

 

 

Summary of Contents for FP-08450

Page 1: ...Fire Detection and Activation System Model 08450 Rev 2 7...

Page 2: ...s 7 3 9 Connecting Multiple FirePro Generators 7 4 Installation 8 5 Wiring Diagram 12 6 Programming 13 7 Operation 13 7 1 LED Indicators 13 7 2 Isolate Function 13 7 3 Reset Function 14 7 4 Test Funct...

Page 3: ...1 3 In Case of Fire If a fire occurs equipment operators should do the following 1 Detection will initiate an alarm condition on the FirePro System 2 The siren strobe will operate and if shutdown rel...

Page 4: ...cted from Stainless Steel Comes with installed Deutsch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit Circuit 1 Alarm...

Page 5: ...wer source 3 3 Siren Strobe Output A siren is required for all marine installations The recommended siren strobe is the Flashni Xenon Sounder Beacon In a typical install the maximum number of supporte...

Page 6: ...The Circuit 2 Alarm Output is a zoned detection circuit capable of operating up to 30 conventional detectors 100 metres of linear heat detection cable or 30 manual call points The Circuit 2 Alarm Out...

Page 7: ...he back of the plug Cables are colour coded for easy identification When installing system cables should be only connected to the correctly coded cable Colour Coding for cables is as follows 3 9 Conne...

Page 8: ...ain Power When panel has been mounted in a suitable location connect main supply power using a Lead to the power input marked red The recommended source for the main power supply input is the vessel s...

Page 9: ...ircuit can be programmed for ALARM ONLY operate siren strobe or AUTOMATIC DISCHARGE discharges suppression system and operates siren strobe If detection is not used the supplied end of line plugs mark...

Page 10: ...ircuit This circuit should remain disconnected until all other circuits are connected The control panel must not be in an alarm fault condition when the FirePro generators are connected as this may ca...

Page 11: ...utput they must be connected using the FP 08919 Splitter Lead See 3 4 Discharge Output for design considerations when connecting multiple FirePro generators The maximum number of FirePro Generators th...

Page 12: ...Page 12 5 Wiring Diagram...

Page 13: ...el Discharging System has initiated activation sequence 7 2 Isolate Function To isolate the control panel press and hold Mode Switch 1 until a 1 beep is heard and the Isolated LED is illuminated To re...

Page 14: ...el to normal operation The test function does not activate the suppression system Note If any LEDS or siren strobes do not operate contact your supplier 7 5 Discharging the Fire System To manually dis...

Page 15: ...esting Perform a manual discharge test by pressing and holding both mode switches continuously for 5 seconds Following the activation sequence ensure the test lamp has operated Isolate the panel to si...

Page 16: ...al details Devices used Date of each inspection Outcome of each inspection Schematic diagrams Photos of the original Installation Programming of the control panel Inspection reports 9 1 Daily Service...

Page 17: ...nal Faults An internal fault cannot be isolated and will display as Internal Sounder Fault LED Fault Continuous steady beep On Internal 5vDC Supply OR Watch Dog Circuit Continuous pulsing beep On Inte...

Page 18: ...nd of line 4k7 Resistor Maximum Detectors per Zone 30 Conventional Detectors 100m Linear Heat Detection 30 Manual Call Points Alarm Threshold 3 6V Fault sensing threshold 0 53V Compatible Detectors Ho...

Page 19: ...l objects contaminated by this material use water and detergent Keep away from food drink and animal feeding stuffs In case of contact with eyes rinse with plenty term of water and contact Doctor or P...

Page 20: ...ed on Circuit 1 Alarm Power Supply In addition to the requirements as per 3 1 Power Supply Input NSCV requires a secondary backup power supply The FP 08870 08871 Power Control Module may be used for c...