background image

 

Local Application Fire System 

FP-08917 

Rev 3.1

 

 

Page  |  3 

2

 

Components 

 

FP-08917 

Local Application system 

1 x FP-08917

 

Y Connector 

2x DP-3000

 

Deutsch Plug 3 Pin M/F, c/w heatshrink 

2x DP-2000

 

Deutsch Plug 2 Pin M/F, c/w heatshrink 

1 x 

 

End-of-line Plug 

Installation & Operators Manual

 

Agent Release Circuit 

 

FP-8919 

Splitter  Cable  for  installaion  of  multiple 
FirePro generators. 

 

FP-08825 

Thermal  Fuse 

  used  to  provide 

signal that system has operated. 

FirePro Condensed Aerosol Generators 

 

FirePro

 

Aerosol

 

Generator

 

20g 

 500g Unit. 

Constructed from S Steel.  Complete with 
Deutsch Plug for easy install.

 

 

FP-6200 

Heavy Duty Bracket 316 SS. 
Suits  FP-100,  200,  500  FirePro  Aerosol 
Generators.

 

 

FirePro Aerosol Generator 

1200g 

 5700g Unit. 

Constructed from S Steel.  Complete with 
Deutsch Plug for easy install.

 

 

FP-6100 

Heavy Duty Bracket 316 SS. 
Suits  FP-1200,  2000,  3000  5700 
FirePro Aerosol Generators.

 

Detection Circuit 

 

FP-9510 

Linear Heat Detection Cable 182° C 
Supplied  in  Cut  Lengths  with  Deutsch 
Plugs for easy install. 
Lengths: 1,2,4,6 & 8m 

 

FP-14053 

Heavy Duty Switch 
including 316 SS Bracket.

 

Installation Components 

Service Components 

 

FP-9500 

2 Hour Fire Rated Shielded Cable. 

 

FP-8800 

System  Test  Module 

  this  unit 

simulates a FirePro generator. 

Signage 

 

FP-8960 

Marine Signage for the System.  A sheet 
of different size labels. 

 

FP-8962 

Cabinet  Signage  for  the  System.    A 
sheet of different size labels. 

3

 

Specifications 

Max Number of FirePro Units 

6v - 1 FP Unit 

12v - 2 FP Units 

24v - 4 FP Units      

Activation Current for FirePro Units 

Max 0.25A 

Max 0.50A 

Max 1.00A 

Quiessant Current 

0 A 

 No current drawn from supply 

Power Supply 

6-30vDC 

Fuse for Power Supply 

5A 

Max Length of Linear Heat Detection 

50m 

Max Number of FP-14053 Switches 

6 switches over 50m 

 

 

Summary of Contents for FP-08917

Page 1: ...ge 1 CONTENTS 1 General Operations 2 2 Components 3 3 Specifications 3 4 Installation 4 5 Servicing Maintenance 5 6 Operation Activation 5 7 Installation of FirePro Generators 6 8 Connection of Multip...

Page 2: ...he switch 1 3 Power Supply designed to operate on 6 to 30vDC supply Number of FirePro units will depend on incoming power supply 1 4 A thermal Fuse FP 08825 may be connected to give a signal that syst...

Page 3: ...ch Plug for easy install FP 6100 Heavy Duty Bracket 316 SS Suits FP 1200 2000 3000 5700 FirePro Aerosol Generators Detection Circuit FP 9510 Linear Heat Detection Cable 182 C Supplied in Cut Lengths w...

Page 4: ...4 5 Manual Actuator s where installed placement is to be carefully considered ensure that it is easily accessible in case of emergency Follow instructios for the installation of the FP 14053 switch 4...

Page 5: ...connected Note the FirePro Simulator stay illuminated until the reset button on the simulator is pressed 5 4 Reconnect the FirePro activation circuit System Logbook A logbook must be kept recording a...

Page 6: ...prompt rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance w...

Page 7: ...e control panel For ease of install servicing and more efficient field wiring Splitter Leads should be installed in areas easy to access and minimise extension leads Installation 8 1 FirePro generator...

Page 8: ...ntre If swallowed IMMEDIATELY contact Doctor or Poisons Information Centre show this container or label This material and its container must be disposed of as hazardous waste FIRST AID MEASURES SWALLO...

Reviews: