Local Application Fire System
FP-08917
Rev 3.1
Page | 7
FP Unit 1
FP Unit 2
FP Unit 1
FP Unit 4
Activation
Cable
Splitter
Lead
Extension Lead
FP Unit 2
Activation
Cable
Extension Lead
Splitter Lead
FP Unit 3
8
Connection of Multiple FirePro Generators
Where multiple FirePro Generators are installed, they must be connected
using the FP-08919 Splitter Lead. The Splitter Lead enables the activation
current to pass to all FirePro generators and for monitoring of the circuit.
Splitter Leads can be installed at any point on the activation circuit and do
not need to be installed adjacent to the fire control panel. For ease of install, servicing and more efficient
field wiring, Splitter Leads should be installed in areas easy to access and minimise extension leads.
Installation
8.1
FirePro generators must remain disconnected until system is completed and fire control panel is
no longer in a fault or alarm condition. The FirePro Universal Test Module (P/N FP-08800) can be
used to take the panel out of a fault condition.
8.2
The supply voltage of any system will determine the wiring which can be used
6vDC Max = 1 FP Units
12vDC Max = 2 FP Units
24vDC Max = 4 FP Units
8.3
Where additional units are required in the system a discharge delay module may be required.
Need to check the system manual for specifications.
8.4
Connection of units
Connection of 2 FirePro Units
Connection of 4 FirePro Units