Local Application Fire System
FP-08917
Rev 3.1
Page | 5
5
Servicing & Maintenance
The FirePro Suppression system should be serviced at least every 6 months in accordance with AS
1851, more often in aggressive environments. Periodic visual inspections of the installed system must
also be conducted by the operators to ensure all installed parts are free from debris, rust, or electrical
faults. Six Monthly servicing must only be undertaken by accredited service technicians.
NO PERSONNEL SHOULD BE IN THE RISK AREA DURING TESTING
UNTIL THE FIREPRO UNITS ARE DISCONNECTED AND TEST MODULES IN PLACE
Servicing and Maintenance Procedure
5.1
Disconnect the FirePro activation circuit (Yellow) at the panel, and connect
the FirePro simulator.
5.2
Visually inspect all installed FirePro Generators, cable, connections,
detection devices and siren/strobes. Look for any signs of damage or wear
and replace as necessary.
5.3
Activate the system
–
after ensuring the FirePro Simulator is connected.
Note: the FirePro Simulator stay illuminated until the reset button on the
simulator is pressed.
5.4
Reconnect the FirePro activation circuit.
System Logbook
A logbook must be kept, recording all the relevant events concerning the installation. The logbook
contains the items required that give a picture and provide for the recording of various things during
the life of the installation. In the logbook you will find the following:
Content of logbook:
•
General details
•
Devices used
•
Schematic diagrams
•
Photos of the Original FirePro Installation
•
Inspection reports
6
Operation -Activation
Should the system be activated :
6.1
Keep the FirePro suppression gas within the risk until the fire is extinguished and not re-ignite.
6.2
In case of emergency, ensure all occupants have left the risk area and where possible alert
emergency services.
6.3
DO NOT open any doors/hatches to the risk area for at least 20 minutes, to prevent re-ignition.
6.4
After 20 minutes, the Aerosol will fall to the ground as dust. Check risk area that is safe and
commence clean-up with warm, soapy water.
6.5
The FirePro Aerosol generators are single use items, so will need to be replaced.