fp_22408_m4.1 

 

     

Page 2 of 10

 

 

The Model 22408 vehicle control panel to provide an integrated fire detection and suppression system.  This control 
panel allows up to 4 FirePro Generators of any size to be installed.  The panel is compliant to AS5062. 
The FIP (fire indicator panel) incorporates-  

 

two monitored detection circuits,

 

 

a monitored activation circuit,

 

 

a monitored power supply circuit with installed 10A fuse

 

 

a monitored 24hr backup battery circuit with battery installed.

 

 

programmable shutdown delay time.

 

 

IN CASE OF FIRE

 

The FirePro Vehicle Suppression System is an automatic system and has Manual switches. 
In case of fire follow these steps: 

1.

 

The Detection system will activate suppression system automatically in case of fire. 

2.

 

Safely Stop the Vehicle and Evacuate all personnel from the vehicle as soon as possible. 

3.

 

Where manual activation required - Remove Travel Pin from Activation Switch and press 
switch. 

4.

 

Keep the FirePro Aerosol within the risk until the fire is completely extinguished or fire 
may reignite. 

5.

 

Wait approximately 20min for the FirePro Aerosol to dissipate and clean up with soapy 
water. 

6.

 

DO NOT open the risk area or attempt to restart the engine, until the fire is completely 
extinguished and the machine has sufficiently cooled.  

7.

 

System will remain in fault until the FirePro generators are replaced.

 

 
SYSTEM OK

 

INDICATOR 

will  indicate  green,  when  the  system  is  receiving  appropriate  24vDC  supply  and  is 

operating normally. If power is not supplied, or a fault if detected the LED will not be lit and the panel will not 
operate or function correctly.  

FIRE INDICATOR

 will indicate red when the detectors go into alarm or a manual activation switch is pressed. 

RELAY RESET

 

INDICATOR 

and  Button.   Pressing  the button will  interrupt  the programmed  shutdown.    This 

delay can be maintained by continuously pressing the button. - indicates that the relay time delay has been reset.   
If the system is in an alarm condition and has been serviced/recharged, the reset button will allow for normal 
vehicle operation. 

ALARM SILENCE

 

INDICATOR 

and Button - will indicate amber when the alarm has been silenced. if pressed, 

the alarm will silence for  6 hours  before sounding  again.  All  other Fault  lights  will continue to indicate that a 
problem is present. 

SERVICE SYSTEM INDICATOR 

- will indicate amber, and activate an alarm, to show that a fault is present.  LED 

will flash in a numbered sequence to indicate which circuit is experiencing a fault (see Fault Codes). 

PUSH TO TEST

 Button - Allows the operator to check functionality of all LED's, relays and alarms without activating 

the system. 

ISOLATION MODE

  -  Pressing  the Amerex Logo button five times will put the panel into 

Isolation Mode.  To 

deactivate Isolation Mode 

 Press and Hold the Amerex Logo Button for 5 seconds.(only for model 22408)

 

 

 

Summary of Contents for FP-22408

Page 1: ...tion Switches 4 Linear Heat Detection Cable 4 Installation of FirePro Units MAX 4 Units 5 Thermal Fuse 5 Relay Connections and Programming 6 Sounder circuit wiring 6 Extension Leads 6 Colour Coded Cab...

Page 2: ...il the FirePro generators are replaced SYSTEM OK INDICATOR will indicate green when the system is receiving appropriate 24vDC supply and is operating normally If power is not supplied or a fault if de...

Page 3: ...plug DO NOT force plugs The panel should not be placed in environments where the temperature is outside the range of 40 C to 66 C Mounting Bracket FP 22408B may be used This bracket will accommodate...

Page 4: ...the cables coming out of the Internal Activation Switch if no External Activation Switch is to be used Switch mechanism with travel Pin Switch Shown in External Mount Mount the Linear Heat Detection...

Page 5: ...he FirePro generator s to the panel using the Activation Circuit marked Yellow For risks that require two or more FirePro generators use the supplied splitter cable s USING Splitter Cables Using the s...

Page 6: ...d this needs to be specified by the installer To create extension leads follow these steps 1 Cut cable to required length and strip outer insulation to approximately 50mm Remove shielding and for 2 Pi...

Page 7: ...late the Model 17310 panel simply unplug the activation cable and this will put the panel into fault This should be done at the connection closest to the panel Control panels do not require any specif...

Page 8: ...Pro Generators and brackets are free from debris and any corrosion Ensure brackets are tight and show no signs of fatigue 5 Inspect Linear Heat Detection Cable ensuring it maintains a closed connectio...

Page 9: ...omes with installed Deutsch Plug for easy install FP 6200 Heavy Duty Bracket 316 SS Suits FP 100 200 500 FirePro Aerosol Generators FP 08960 Signage for the System A sheet of different size labels FP...

Page 10: ...icle ID Number Date of Installation FirePro Units Installed Specify Size and No of units Manual Activation Specify Location of Manual Actuation Switches Shutdown Installation Specify Delay Time and Sh...