In the event of a system alarm or system service the audible alarm can be silenced with the “Alarm Silence” button. 

When the “Alarm Silence” button is depressed, the “Alarm Silence”  LED will illuminate and  the other

  LEDs will 

continue to show the alarm or service system fault status. The alarm will remain silent for 6 hours and will then 

resound to remind personnel that a problem condition is present

.

 

 

Model 22408 ONLY.  Pressing the Amerex Logo button five times will put the panel into 

Isolation Mode. 

During isolation mode the following panel conditions will be in effect: 

 

The green System OK LED will blink continuously indicating the panel has power but is in isolation mode. 
The Amber colored Service System LED will stay steady on. The audible alarm will chirp every 30 seconds 
to indicate the panel is in isolation mode. 

 

In isolation mode the firing circuit is disabled.  All other circuits, (detection, pressure switch, relay) remain 
operational.  Isolation mode can be used for testing, transportation, machine maintenance etc. 

 

In isolation mode if either detection circuit is activated the red FIRE LED will illuminate, the audible alarm 

will sound and the relay will begin countdown.  This condition would remain until the source of the alarm 
is cleared. 

 

The panel will remain in isolation mode until mode is deactivated. 

 

To deactivate mode

, insure the red FIRE LED is not illuminated, press and hold the Amerex Logo button 

for five seconds.  Panel returns to normal mode green LED System OK illuminated unless fault condition 
are present.  If fault conditions are present, panel flashes standard fault codes at the Service System LED. 

 

Relay Transfer (engine shutdown) is indicated by a RED LED at the Relay Reset Button. 

To Isolate the Model 17310 panel simply unplug the activation cable 

 and this will put the panel into fault.  This 

should be done at the connection closest to the panel. 

 

Control panels do not require any specific maintenance but should the control panel become dirty it can be wiped 

over with a damp cloth and should then be dried with a dry, lint free cloth.  Detergents or solvents should not be 
used to clean the panel and care must be taken that water does not 

Enter the enclosure. 

Testing  of  the  extinguishant  system  should  only  be  carried  out  by  trained  personnel  and  must  be  done  with 
appropriate isolation measures in place to ensure that accidental discharge of the extinguishant agent is avoided 
and any malfunction should be reported to the fire alarm maintenance company immediately. 

 

TroubleShooting & Fault Codes 

In  the  event  of  a  system  fault  in  any  of  the  supervised  circuits,  an 

audible alarm will sound and the yellow "Service System" LED will flash 
once  every  ten  seconds  in  a  coded  sequence  to  indicate  the  circuit 
presenting with a fault. 
If a fault is detected there is a five second delay before notification. For 
power supply faults, the delay for notification is 20 seconds. 

The  audible  alarm  can  be  silenced  with  the  “Alarm  Silence”  button. 
When pressed, the “Alarm Silence” LED will illuminate and the other 

Fault LEDs will remain on. The alarm will remain silent for 6 hours and 
will then resound to remind personnel that a fault condition is present. 

 

 

This battery should be 

replaced every 2 years

 to ensure proper system function or if the 

panel indicates that there is a fault in the backup circuit.  To replace: 

1.

 

Remove the four screws on the front of the panel to remove the front cover.  

2.

 

Disconnect the battery connector and remove old battery.   

3.

 

Replace battery (P/N 18156). 

4.

 

Reconnect the battery and replace the front cover. 

5.

 

Check the "Service System" LED on the front of the panel.  If installed correctly, there will be no fault. 

 

Summary of Contents for FP-22408

Page 1: ...tion Switches 4 Linear Heat Detection Cable 4 Installation of FirePro Units MAX 4 Units 5 Thermal Fuse 5 Relay Connections and Programming 6 Sounder circuit wiring 6 Extension Leads 6 Colour Coded Cab...

Page 2: ...il the FirePro generators are replaced SYSTEM OK INDICATOR will indicate green when the system is receiving appropriate 24vDC supply and is operating normally If power is not supplied or a fault if de...

Page 3: ...plug DO NOT force plugs The panel should not be placed in environments where the temperature is outside the range of 40 C to 66 C Mounting Bracket FP 22408B may be used This bracket will accommodate...

Page 4: ...the cables coming out of the Internal Activation Switch if no External Activation Switch is to be used Switch mechanism with travel Pin Switch Shown in External Mount Mount the Linear Heat Detection...

Page 5: ...he FirePro generator s to the panel using the Activation Circuit marked Yellow For risks that require two or more FirePro generators use the supplied splitter cable s USING Splitter Cables Using the s...

Page 6: ...d this needs to be specified by the installer To create extension leads follow these steps 1 Cut cable to required length and strip outer insulation to approximately 50mm Remove shielding and for 2 Pi...

Page 7: ...late the Model 17310 panel simply unplug the activation cable and this will put the panel into fault This should be done at the connection closest to the panel Control panels do not require any specif...

Page 8: ...Pro Generators and brackets are free from debris and any corrosion Ensure brackets are tight and show no signs of fatigue 5 Inspect Linear Heat Detection Cable ensuring it maintains a closed connectio...

Page 9: ...omes with installed Deutsch Plug for easy install FP 6200 Heavy Duty Bracket 316 SS Suits FP 100 200 500 FirePro Aerosol Generators FP 08960 Signage for the System A sheet of different size labels FP...

Page 10: ...icle ID Number Date of Installation FirePro Units Installed Specify Size and No of units Manual Activation Specify Location of Manual Actuation Switches Shutdown Installation Specify Delay Time and Sh...

Reviews: