Summary of Contents for FPC-2

Page 1: ...Maintenance Manual Table of Contents 1 Introduction 2 2 Operation 2 3 Panel Operation 2 4 Installation and Mounting 3 5 Installation of FirePro Generators 5 6 Connecting to Master Fire Panel 6 7 Maint...

Page 2: ...r heat detection cable or smoke detector the red Fire indicator will be lit the FirePro Aerosol Generators will operate and immediately discharge extinguishing Aerosol into the protected area the inte...

Page 3: ...erminals along the top of the circuit board Cabling must comply with the Australian Standards The resistance of any cable must not exceed 25 ohms Terminals are capable of accepting wires of up to 2 5m...

Page 4: ...or other device Cabling Requirements Cable Requirements All cabling in the FirePro Installation MUST be done using 0 75mm shielded Fire Rated Cable Care taken to ensure that all cables are isolated a...

Page 5: ...t rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance with re...

Page 6: ...Control port on the Detection card top card or by releasing the read switch by opening the inner Perspex door 1 Move the Write Enable switch to the right on the Detection Card top card The System Mod...

Page 7: ...will require connection back to the master panel To make the FPC 2 compatible with an addressable input module move jumpers J1 and J2 from their default positions position A to position B The FIRE NO...

Page 8: ...e fuse will blow on EACH test Note If the system has been activated the system activation fuse needs to be inspected as blown fuse will show as a fault The Fuse is 1 6AMP Quick Blow 9 Specifications M...