Fire Control Panel 

FP-C2 

Rev 7.0

 

 

 

 

Page  |  

 

1.

 

Introduction 

The FPC-2, a fire alarm control panel with Extinguishant Control Unit and Aerosol Agent Controller, is designed to comply 
with AS4487(2013) - Control and Indicating Equipment.  The control equipment is a combined fire alarm control panel 
and extinguishant system with one detection zones, and one extinguishant zone. 
The FPC-2 Panel Protection Controller enables monitoring of detection and extinguishing circuits.  

The panel will support 

up to 4 

FirePro aerosol

 

generators.  

The FPC-2 requires a battery backed 24V DC power supply capable of delivering 

3A for a short period in order to operate the Aerosol Generators.  Volt free contacts are available to signal fire and fault 
conditions to plant or other monitoring equipment. Jumper links allow a signal to an addressable input module via a 
simple, 2 wire connection. 
An Isolate Key switch - located on the front of control panel 

 allows for the isolation the four extinguishant outputs for 

service or maintenance purposes. 

2.

 

Operation 

Under normal circumstances, the green Power On indicator will be lit, 

and the internal buzzer will be silent. 

The wiring to the detection circuit and to the FirePro

 

Aerosol Generators is supervised and disconnection of any of this 

wiring will be shown by illumination of the yellow Fault indicator on the front panel and operation of the internal buzzer.  
The internal fault volt free contact will operate and signal any external equipment that is connected  to the controller 

Internal indicators are provided to show whether it is the detection circuit wiring or the wiring to the Aerosol Generators 
that has a fault. 
The buzzer may be silenced by pressing the Buzzer Silence button. 
Upon activation of a linear heat detection cable or smoke detector, the red Fire indicator will be lit, the FirePro

 

Aerosol 

Generators will operate and immediately discharge extinguishing Aerosol into the protected area, the internal buzzer will 
sound and the Fault indicator will illuminate, indicating that the Aerosol Generators have fired and need replacing. 
The internal fire volt free contact will operate and signal any external equipment that is connected to the controller. The 

buzzer may be silenced by pressing the Buzzer Silence button.  Following a fire activation and replacement of the FirePro

 

Aerosol Generators the system can be returned to normal operation by operating the Reset button on the front of the 
controller. 
Operating  the  Isolate  key-switch  by  turning  the  key  anti-

clockwise  from  ‘Live’  to  ‘Off’  isolates  the  four  extinguishant 

outputs thereby preventing discharge. This mode should only be used for service, maintenance, or temporary purposes - 

In the ‘Off’ position and where the detection

 circuit is activated, extinguishant outputs 

will not operate

With the Isolate key-

switch in the ‘Off’ position and where the detection circuit is activated, the internal volt free contact 

will  continue  to  operate  (change  over).  The  Reset  and  Buzzer  Silence  buttons  will  continue  to  be  operational,  when 
pressed. 
Note: The controller will continue to show a fault condition until the Aerosol Generators are replaced. 

3.

 

Panel Operation 

 

 

Silence Alarms 

The 

Silence/Sound alarm

 button will only silence the buzzer in the FPC-2 unit. 

 

Reset 

To 

Reset

 button is a full reset on the FPC-2 panel only. 

 

Indications 

Power Indicator 

Operates as long as voltage is coming into panel 

 range is 12-30vDC. 

Fault Indicator  

Operates whenever any circuit fault is detected in the system.  It is a common indictor for both the 
activation and detection circuits.  The fault indication will operate when the system is isolated. 

Fire Indicator 

Operates when the detection circuit goes into alarm. 

 

Summary of Contents for FPC-2

Page 1: ...Maintenance Manual Table of Contents 1 Introduction 2 2 Operation 2 3 Panel Operation 2 4 Installation and Mounting 3 5 Installation of FirePro Generators 5 6 Connecting to Master Fire Panel 6 7 Maint...

Page 2: ...r heat detection cable or smoke detector the red Fire indicator will be lit the FirePro Aerosol Generators will operate and immediately discharge extinguishing Aerosol into the protected area the inte...

Page 3: ...erminals along the top of the circuit board Cabling must comply with the Australian Standards The resistance of any cable must not exceed 25 ohms Terminals are capable of accepting wires of up to 2 5m...

Page 4: ...or other device Cabling Requirements Cable Requirements All cabling in the FirePro Installation MUST be done using 0 75mm shielded Fire Rated Cable Care taken to ensure that all cables are isolated a...

Page 5: ...t rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance with re...

Page 6: ...Control port on the Detection card top card or by releasing the read switch by opening the inner Perspex door 1 Move the Write Enable switch to the right on the Detection Card top card The System Mod...

Page 7: ...will require connection back to the master panel To make the FPC 2 compatible with an addressable input module move jumpers J1 and J2 from their default positions position A to position B The FIRE NO...

Page 8: ...e fuse will blow on EACH test Note If the system has been activated the system activation fuse needs to be inspected as blown fuse will show as a fault The Fuse is 1 6AMP Quick Blow 9 Specifications M...