Fire Control Panel
FP-C2
Rev 7.0
Page |
4
Detection zone wiring
These terminals are for the connection of a conventional type 24V smoke
detectors or linear heat detection cable.
The wiring is monitored for open circuit faults.
The 6K8 end of line resistor are factory fitted to the control panel
’
s terminals
must be removed and placed across the last device that is wired to the
circuit.
Detection circuit must be wired as a single, radial circuit with no spurs or T
junctions to enable the monitoring circuit to work correctly.
Convention detectors may be mixed Thermal and Smoke.
A short circuit will create an ALARM condition.
Sounder circuit wiring
There is no dedicated Siren circuit on this panel. Using the
Fire Relay, a siren can be connected.
The “FIRE” terminal on the FPC2 is a relay that creates a
closed circuit upon activation of the panel.
This can be used to activate a siren or other device.
Cabling Requirements
Cable Requirements - All cabling in the FirePro Installation MUST
be done using 0.75mm shielded Fire Rated Cable. Care taken to
ensure that all cables are isolated, and that RF shielding on cable
is stripped back to ensure that there is not accidental grounding.
Cables are colour coded for easy identification.
Extension Leads - Deutsch Plugs must be used to ensure water-
proof connections are made throughout the installation.
Fault relay
The Fault Relay
is normally energised and will de-energise upon any fault condition including total loss of power.
Volt
free changeover contact that will operate whenever there is a fault condition. This contact is rated for a
maximum of 30V DC and 1Amp
.
These ratings must not be exceeded
Fire relay
The Fire Relay will energise upon activation of a fire condition. The relay will remain activated until the control panel is
reset. Volt free changeover contact that will operate whenever the system is triggered to alarm. This contact is rated
for a maximum of 30V DC and 1Amp
.
These ratings must not be exceeded.