Page  |  

 

Power Connection from Sigma XT 

When FP-C2 is used as a sub-panel from a Sigma XT Control panel it should be connected to a separate Detection Zone 
as described earlier.  Power can be taken from the Sigma panel as shown.   

Power can come from 1, 2 , or 3. 

 

CANNOT USE - AUX 24v from Exting Module as it is current limited to 100mA, 

Power from main panel will provide battery backup. 

 

FPC-2 as activation Module only 

This configuration uses the FPC-2 as an activation module  only.  This can be established with any style of AS Panel.  
Individual configurations will be dependent on the specifics of the master panel. 
Connection will be required for the Power Supply.  The activation device needs to 
connect to the detection circuit on the FPC-2, this needs to meet the detection circuit 

criteria.  Once the FPC-2 receives a detection advice 

 activation of the extinguishant 

system is immediate. 
Fire and Fault reporting will require connection back to the master panel. 
To make the 

FPC-2 

compatible with an addressable input module, move jumpers 

J1 and J2 from their default positions (position A) to position B. The FIRE NO and C 
terminals can now be connected directly to the addressable input module. 
Alarm and fault conditions will be indicated on a addressable fire alarm control panel. 
Note: The volt free contact function is not available when the contacts are being 
used to signal and addressable input module. 
 

 

7.

 

Maintenance 

FPC-2 control panels do not require any specific maintenance, but should the control panel become dirty it can be wiped 

over with a damp cloth and should then be dried with a dry, lint free cloth.  Detergents or solvents should not be used to 
clean the panel and care must be taken that water does not 

Enter

 the enclosure. 

Testing of the extinguishant system should only be carried out by trained personnel and must be done with appropriate 

isolation measures in place to ensure that accidental discharge of the extinguishant agent is avoided and any malfunction 
should be reported to the fire alarm maintenance company immediately. 

 

Summary of Contents for FPC-2

Page 1: ...Maintenance Manual Table of Contents 1 Introduction 2 2 Operation 2 3 Panel Operation 2 4 Installation and Mounting 3 5 Installation of FirePro Generators 5 6 Connecting to Master Fire Panel 6 7 Maint...

Page 2: ...r heat detection cable or smoke detector the red Fire indicator will be lit the FirePro Aerosol Generators will operate and immediately discharge extinguishing Aerosol into the protected area the inte...

Page 3: ...erminals along the top of the circuit board Cabling must comply with the Australian Standards The resistance of any cable must not exceed 25 ohms Terminals are capable of accepting wires of up to 2 5m...

Page 4: ...or other device Cabling Requirements Cable Requirements All cabling in the FirePro Installation MUST be done using 0 75mm shielded Fire Rated Cable Care taken to ensure that all cables are isolated a...

Page 5: ...t rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance with re...

Page 6: ...Control port on the Detection card top card or by releasing the read switch by opening the inner Perspex door 1 Move the Write Enable switch to the right on the Detection Card top card The System Mod...

Page 7: ...will require connection back to the master panel To make the FPC 2 compatible with an addressable input module move jumpers J1 and J2 from their default positions position A to position B The FIRE NO...

Page 8: ...e fuse will blow on EACH test Note If the system has been activated the system activation fuse needs to be inspected as blown fuse will show as a fault The Fuse is 1 6AMP Quick Blow 9 Specifications M...

Reviews: