Fire Control Panel 

FP-C2 

Rev 7.0

 

 

 

 

Page  |  

4.

 

Installation and Mounting 

This equipment is designed to be operated from 24V DC supply.  This power 
supply must be battery backed. 
The FPC-2 should be effectively bonded to earth.  Failure to ensure that all 

conductive  accessible  parts  of  this  equipment  are  adequately  bonded  to 
earth will render the equipment unsafe. 
This  control  panel  is  designed  for  indoor  use  only  and  at  temperatures 
between  -5

0

C  (+/-  3)  and  +40

0

C  (+/-2)  and  with  a  maximum  relative 

humidity of 95%.  Panels is rated to IP30 and suitable for mounting indoors.  
Operation outside of these limits may render the equipment unsafe. 

MOUNTING

 

 Panel must be securely mounted. 

Cables should be connected using cable glands fitted to the knockouts. 
 

DIMENSIONS - 200H x 150W x 50D mm 

 

Connecting to the circuit board 

All  connections  for  field  wiring  are  to  a 

single row of terminals along the top of the 
circuit board. 
Cabling  must  comply  with  the  Australian 
Standards.    The  resistance  of  any  cable 
must not exceed 25 ohms. 
Terminals are capable of accepting wires of 
up to 2.5mm

2

 
 
 
 
 

 

Power 24v IN 

 24v OUT 

The polarity of these terminals is very important.  The 24V IN is for connection of the power from a previous unit or a 
power supply and the 24V OUT is for connection to further units. 
Max Number  of FPC-2  Units chained  together  is 3  using  the power  IN / OUT link.  For  additional units need  to wire 
separately.  Power supply will need to consider what current is required to ensure all devices operate correctly. 

 

Connection of Aerosol Units to Activation circuit 

These terminals are  for the connection  of  FirePro®

 

Aerosol 

Generators. Test lamps are provided in the terminals to allow 
testing  of  the  system  before  connecting  the  FirePro®

 

generators.  These  test  lamps  should  be  removed  from  the 
terminals if a FirePro®

 

Aerosol Generator is to be fitted. 

Any  FirePro®

 

generator  outputs  that  are  not  being  used 

should be left with test lamps fitted. 

 
 
 
 

Summary of Contents for FPC-2

Page 1: ...Maintenance Manual Table of Contents 1 Introduction 2 2 Operation 2 3 Panel Operation 2 4 Installation and Mounting 3 5 Installation of FirePro Generators 5 6 Connecting to Master Fire Panel 6 7 Maint...

Page 2: ...r heat detection cable or smoke detector the red Fire indicator will be lit the FirePro Aerosol Generators will operate and immediately discharge extinguishing Aerosol into the protected area the inte...

Page 3: ...erminals along the top of the circuit board Cabling must comply with the Australian Standards The resistance of any cable must not exceed 25 ohms Terminals are capable of accepting wires of up to 2 5m...

Page 4: ...or other device Cabling Requirements Cable Requirements All cabling in the FirePro Installation MUST be done using 0 75mm shielded Fire Rated Cable Care taken to ensure that all cables are isolated a...

Page 5: ...t rescue of any trapped personnel shall be provided including Adequate aisle ways routes of exit Alarms audible and visual that operate immediately on detection of the fire Signs in accordance with re...

Page 6: ...Control port on the Detection card top card or by releasing the read switch by opening the inner Perspex door 1 Move the Write Enable switch to the right on the Detection Card top card The System Mod...

Page 7: ...will require connection back to the master panel To make the FPC 2 compatible with an addressable input module move jumpers J1 and J2 from their default positions position A to position B The FIRE NO...

Page 8: ...e fuse will blow on EACH test Note If the system has been activated the system activation fuse needs to be inspected as blown fuse will show as a fault The Fuse is 1 6AMP Quick Blow 9 Specifications M...

Reviews: