Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 12 of 18
4.1
System Test
Step 1
Power off the unit.
Step 2
Turn
Isolate Key Switch
to “Off” position.
Step 3
Disconnect the FirePro Generators and ensure that the test lamps are
fitted to the terminals.
Step 4
Ensure both jumper links (J1 & J2) are fitted in position A
Step 5
Inspect all system components (Detectors, Sirens etc.) and all cables for
signs of damage.
4.2
Release Test
Step 6
Power on the unit.
Step 7
Turn
Isolate Key Switch
to “Live” position.
Step 8
Trigger the detection input by operating a smoke detector or linear heat
detector.
Step 9
Ensure both jumper links (J1 & J2) are fitted in position A
Step 10
Inspect all system components (Detectors, Sirens etc.) and all cables for
signs of damage.
4.3
Detector monitoring Test
Step 11
Disconnect the wiring to the detector and ensure that the yellow Fault LED
on the front panel and the internal yellow LED marked LED4 are lit and the
buzzer sounds.
Step 12
Press the
Silence Buzzer
button and ensure the buzzer silences.
Step 13
Re-connect the detector wiring and ensure that the fault indications clear.
IMPORTANT
ALL TECHNICAL CHECKS MUST COMPLY WITH APPLICABLE
LOCAL CODES, REGULATIONS AND SPECIFIC PROJECT
REQUIREMENTS