Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 13 of 18
4.4
Condensed Aerosol Generator
monitoring Test
Step 14
Disconnect one of the test lamps and ensure that the yellow Fault LED on
the front panel and the internal yellow LED marked LED5 are lit and the
buzzer sounds.
Step 15
Press the
Silence Buzzer
button and ensure the buzzer silences.
Step 16
Re-connect the test lamp and ensure that the fault indications clear.
Step 17
Turn the
Isolate Key Switch
to the “Off” position and ensure the that the
yellow fault LED on the front panel and the internal yellow LED marked
LED5 are lit and the buzzer sounds.
Step 18
Turn the
Isolate Key Switch
to the “Live” position and ensure that the
fault indication clears.