Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 14 of 18
5. Testing and Commissioning
5.1
System test
Step 1
Power off the unit.
Step 2
Turn the
Isolate Key Switch
to the “Off” position.
Step 3
Remove the front frame panel.
Step 4
Disconnect the FirePro Generators and ensure the test lamps are fitted to
the terminals.
Step 5
Inspect all components – detectors, sirens etc.
Step 6
Inspect cables for signs of damage.
Step 7
Inspect panel fuse and check if it has blown.
Step 8
Power on the unit.
Step 9
Turn Isolated Key Switch to the “Live“ position.
Step 10
Trigger the detection input by operating a smoke detector linear heat
detector.
Step 11
Ensure that the test lamps connected to the FirePro GEN1 terminals light
immediately, the red fire indicator on the panel is lit, the yellow fault
indicator is lit and the buzzer sounds.
Step 12
Press the
Silence Buzzer
button to silence the buzzer and then the
Reset
button
to reset the system.
Step 13 Disconnect the wiring to the detector and ensure that the yellow Fault LED
on the front panel and the internal yellow LED marked LED4 are lit and the
buzzer sounds.
Step 14
Press the
Silence Buzzer
button and ensure the buzzer silences.
Step 15
Re-connect the detector wiring and ensure that the fault indication clears.
Step 16
Disconnect one of the test lamps and ensure that the yellow Fault LED on
the front panel and the internal yellow LED marked LED5 are lit and the
buzzer sounds.
Step 17 Press the Silence Buzzer button and ensure the buzzer silences.
Step 18 Re-connect the test lamp and ensure that the fault indication clears.
Step 19 Turn
Isolate Key Switch
to “Off” position and ensure that the yellow Fault
LED on the front panel and the internal yellow LED marked LED5 are lit and
the buzzer sounds.
Step 20
Turn
Isolate Key Switch
to “Live” position and ensure that the fault
indication clears.