Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 3 of 18
Overview
The
FirePro
FPC-2 V2 Fire Extinguishant Controller enables monitoring detection and
automatic extinguishing of a fire in an electrical cabinet or small enclosure using linear
heat detection cable or automatic smoke detectors and
FirePro
Condensed Aerosol
Generators.
The FPC-2V2 has one detection input for connection of linear heat detection cable, smoke
detectors or a combination of both, which is monitored for disconnection of the detection
devices.
Four outputs are provided for the connection of
FirePro
Condensed Aerosol Generators and
disconnection of any of these will announce a fault condition.
The FPC-2V2 requires a battery backed 24 V DC power supply capable of delivering a
minimum of 1.6A for a short period to operate the Condensed Aerosol Generators.
Terminals are provided for incoming and outgoing connection of the 24 V DC power
supply.
Volt free contacts are available to signal fire and fault conditions to plant or other
monitoring equipment. By selecting the appropriate jumper link arrangement, it is
possible to signal an addressable input module via a simple 2 wire connection.
An Isolate Key switch - located on the front of control panel – allows for the isolation
the four extinguishant outputs for service or maintenance purposes.
The FPC-2V2 conforms to the essential requirements of the EMC Directive 2014/30/EU
and are manufactured at an ISO9001 and ISO14001 certified facility of Kentec
Electronics Limited. The declaration of conformity is issued under the sole
responsibility of the manufacturer.