Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
Page 4 of 18
1. Operation
Under normal circumstances only the green Power On indicator will be lit, none of the
outputs will be operated and the internal buzzer will be silent.
The wiring to the detection circuit and the
FirePro
Condensed Aerosol Generators is
supervised and disconnection of any of this wiring will be shown by illumination of the
yellow Fault indicator on the front panel and operation of the internal buzzer.
The internal fault volt free contact will operate and signal any external equipment that is
connected to the controller. Internal indicators are provided to show whether it is the
detection circuit wiring or the wiring to the Condensed Aerosol Generators that has a
fault.
The buzzer may be silenced by pressing the Buzzer Silence button.
Upon activation of a linear heat detection cable or smoke detector the red Fire indicator
will be lit, the
FirePro
Condensed Aerosol Generators will operate and immediately
discharge extinguishing Aerosol into the protected area. The internal buzzer will sound,
and the Fault indicator will illuminate indicating that the Condensed Aerosol Generators
have fired and need replacing.
The internal fire volt free contact will operate and signal any external equipment that is
connected to the controller.
The buzzer may be silenced by pressing the Buzzer Silence button.
Operating the Isolate key-switch by turning the key anti-clockwise from ‘Live’ to ‘Off’
isolates the four extinguishant outputs thereby preventing discharge. This mode should
only be used for service, maintenance, or temporary purposes - In the ‘Off’ position and
where the detection circuit is activated, extinguishant outputs
will not operate
.
With the Isolate key-switch in the ‘Off’ position and where the detection circuit is
activated, the internal volt free contact will continue to operate (change over). The Reset
and Buzzer Silence buttons will continue to be operational, when pressed.
Following a fire activation and replacement of the
FirePro.
Condensed Aerosol Generators
the system can be returned to normal operation by operating the Reset button on the
front of the controller.
Note:
The controller will continue to show a fault condition until the Condensed Aerosol
Generators are replaced.