Kiwa
®
declaration
K94463/05
Page 6 of 6
FirePro Ignition device for Non-Pressurized Condensed Aerosol
Generators
Chapter
Description
Demand
1)
Result
Remarks
7.
Test methods
7.15
Ignition performance test
A
Pass
25 samples of the complete
ignition devices:
•
Bi-metal switch,
•
Heat cable and
•
BTA ignition device (Bulb
Thermal Activator)
The bi-metal switch and heat cable
are mandatory equipped with the
FPC-5 ignition device.
Bi-metal switch is tested including
an extension cable for bi-metal
element
with a maximum length of
10 meters and up to 3 bi-metal
switch elements in multiple
(parallel) configuration.
Heat cable is tested with a
maximum length of 10 meters
including the length of the
extension cable. Variations are
allowed.
All operate as intended.
1)
A = Applicable
N/A = Not Applicable
Not tested