7.

 

Alternative Sign Arrangements 

 

Mimic Signs / Connecting more than 7 Signs 

In systems that require more than 7 signs, additional signs may be installed by connecting to the 24VDC TRIGGER 
terminals located in each sign.  This allows connected signs to mimic the operation of a sign that is connected to 

the STATUS SERIAL (RS485) 

circuit.  Note: signs can only mimic other signs of the same type (A “Do Not Enter” 

Sign can only mimic another “Do Not Enter” Sign).

 

The 24VDC trigger function of each sign connected to the  STATUS SERIAL (RS485)  circuit can support up to 3 
additional signs. 
There  is  no  need  to  configure  the  address  or  sign  function  switches,  however  the  internal  buzzer  and  flashing 
functions can still be adjusted separately. 
IMPORTANT 

 An additional external power supply OR an upgraded power supply in the FIP is required for any 

additional devices over the standard maximum of 7 devices. Each sign has a current draw of 140mA. When installing, 
power supply (including backup supply) must be assessed to ensure that it will be adequate. 
While it is possible to use this configuration with fewer than 7 devices, it is not recommended. 
The LCS must be installed on the STATUS SERIAL (RS485) circuit.  It cannot be used as a mimic device.   

 
 

 
 

 
 

  

 

24VDC Trigger Terminals 

+

 

Power Supply 

Controls 

LOWER

 half of mimic sign 

Controls 

UPPER

 half of mimic sign 

Summary of Contents for Sigma XT

Page 1: ...Fire Alarm and System Warning Signs Local Control Stations Installation and Operations Manual Serial Communications Type SIGMA XT FP Issue 3 5 March 2020...

Page 2: ...CS 7 Power and Data Connection 7 Connection to Hold and Mode inputs 8 Mode input 8 Hold input 8 Mode select keyswitch 8 Manual release 8 Processor and Watchdog Reset Switches 9 Internal fault indicati...

Page 3: ...tatus units have monitored inputs to which remote Hold or Mode select switches can be connected These inputs are monitored for open and short circuit faults and therefore need to have a 470R 1W trigge...

Page 4: ...Signs Mount Sunshade Remove cover and Internal circuit board Mount using suitable fixings ONLY Mount to sunshade surface if the enclosure is twisted on mounting it will crack over time Best practice...

Page 5: ...he corresponding terminals at the control panel Connecting Signs with RS485 Serial 3 1 1 Connecting up to 3 Signs For systems requiring up to 3 signs or devices to be installed wiring is as follows No...

Page 6: ...WN BEFORE ANY CHANGES TO SIGNS Connections for the first 3 signs or devices remains the same as the previous wiring diagram For more than 3 signs a separate power supply is required from the 24VDC out...

Page 7: ...r systems requiring a LCS to be installed wiring is as follows Notes FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If installed as one of the first 3 devices on the STATUS SERIAL RS485 circuit...

Page 8: ...e inputs Therefore for the system to be in Automatic and manual mode all Mode inputs must be inactive Indication of the Mode is given on the front of the status unit by the Manual only or Automatic an...

Page 9: ...e located along the bottom of the PCB and are as follows 4 8 1 COM This LED indicates that the data communications connection to the control panel is not present This may be because the data lines are...

Page 10: ...ERED DOWN BEFORE ANY CHANGES TO DEVICES IMPORTANT Devices with the same address will cause an intermittent fault to be displayed Assigning Sign Function In addition to addressing signs connected to th...

Page 11: ...utton on the module to view the faults If status units are detected the LCD will display X the address of the status unit found To accept the status units found slide the WRITE ENABLE switch on the mo...

Page 12: ...p to 3 additional signs There is no need to configure the address or sign function switches however the internal buzzer and flashing functions can still be adjusted separately IMPORTANT An additional...

Page 13: ...cables for the RS485 circuit with the FIP effectively in the middle of the circuit rather than at one end FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If process is done with power connected...

Page 14: ...ame as another device in the 485 circuit Power has failed to the LCS RS485 signal has failed to the LCS 9 Specifications Internal Sign External Sign Local Control Station Size 195 x 300 x 50mm 195 x 3...