1.

 

Introduction 

SIGNS

  -  The  illuminated  warning  signs  provide  a  clear,  visual  and  audible  warning  for  a  fire  alarm, 

extinguishant  release, and System inoperative.  Signs have two levels of operation in which the top and bottom 
halves of the sign may be split to show an initial warning and then additional text for a  reinforced warning, or 
both halves can be activated at  once. 

LOCAL CONTROL STATION

 (LCS) may be required by standards for an installation.  These units can be installed 

using the serial bus and can be inserted anywhere in the 485 circuit. 
A maximum of 7 devices (signs/LCS) can be installed when utilising the 485 Circuit. 

 

Sign Locations 

Locations where signs must be installed are defined by AS 1670.  This manual does not replace reading the full 
standard.  Signs should be firmly mounted in appropriate locations.  Interior signs are rated IP30 and are designed 

for indoor use only.  Weatherproof Signs are available.  Signs are considered by the Sigma XT FIP to be OUTPUT 
UNIT(S) 

“FIRE ALARM/DO NOT ENTER” SIGNS

 - Installed outside the risk area, adjacent to all egress points and clearly 

visible to anyone who may enter the risk area. 

“FIRE ALARM/EVACUATE AREA” SIGNS

 - Installed inside the risk area, adjacent to all egress points and clearly 

visible to all occupants of the risk area. 

“EXTINGUISHING SYSTEM INOPERATIVE” SIGNS 

- Installed adjacent to the FIP and egress points, with additional 

signs where necessary to be clearly visible to anyone who enters the risk area. 

 

Local Control Stations (LCS) 

LCS should be mounted firmly in an accessible location. The LCS is considered by the Sigma XT FIP to be a STATUS 
UNIT(S).  Status units  have monitored inputs to which remote Hold or Mode select switches can be connected. 
These inputs  are monitored for  open and short circuit  faults and therefore  need  to  have a  470R  1W trigger 

resistor connected in series with  the activating, normally  open switches and 6K8 0.5W  end of line monitoring 
resistors connected across the  end  of the  cables. 
Status Units are environmental class A and are designed for indoor use only at temperatures between -5

0

C (+/- 3) 

and +40

0

C (+/- 2) and with a maximum relative humidity of 95%.  The IP rating for the enclosure is IP30.  Operation 

outside of these limits may render the equipment unsafe. 
The 6K8 end-of-line monitoring  resistors are supplied fitted to the Hold  and Mode  input terminals  

 

External Devices 

In  addition  to  standard  installation  rules,  there  are  some  additional  precautions  that  must  be  observed  when 
installing external signs. 
SUNLIGHT - If an external sign is mounted in direct sunlight, it may be difficult to see if the sign is illuminated.  In 
this case it may be necessary to install a sun shield to make the illuminated sign visible. 
DRIP LOOP - All external devices should be installed with cable penetrations coming through the bottom of the 
sign, with a drip loop included to avoid the accumulation and ingress of water that may damage the electronics. 

 

Cable Penetrations and Terminations 

All cable penetrations into the sign enclosures must be protected by cable glands or bushings.  Each sign enclosure 
features  a  series  of  20mm  knockouts  to  accommodate  these  cable  glands.    The  max  size  of  cable  that  the 
terminals will accommodate  is 2.5mm.   
When preparing cable terminations, ensure that cables are not going to cross the front surface of the circuit board 
as this will impair the light output of the unit, and the shadows generated by the cables will be clearly visible when 
the sign is lit. 

 

Summary of Contents for Sigma XT

Page 1: ...Fire Alarm and System Warning Signs Local Control Stations Installation and Operations Manual Serial Communications Type SIGMA XT FP Issue 3 5 March 2020...

Page 2: ...CS 7 Power and Data Connection 7 Connection to Hold and Mode inputs 8 Mode input 8 Hold input 8 Mode select keyswitch 8 Manual release 8 Processor and Watchdog Reset Switches 9 Internal fault indicati...

Page 3: ...tatus units have monitored inputs to which remote Hold or Mode select switches can be connected These inputs are monitored for open and short circuit faults and therefore need to have a 470R 1W trigge...

Page 4: ...Signs Mount Sunshade Remove cover and Internal circuit board Mount using suitable fixings ONLY Mount to sunshade surface if the enclosure is twisted on mounting it will crack over time Best practice...

Page 5: ...he corresponding terminals at the control panel Connecting Signs with RS485 Serial 3 1 1 Connecting up to 3 Signs For systems requiring up to 3 signs or devices to be installed wiring is as follows No...

Page 6: ...WN BEFORE ANY CHANGES TO SIGNS Connections for the first 3 signs or devices remains the same as the previous wiring diagram For more than 3 signs a separate power supply is required from the 24VDC out...

Page 7: ...r systems requiring a LCS to be installed wiring is as follows Notes FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If installed as one of the first 3 devices on the STATUS SERIAL RS485 circuit...

Page 8: ...e inputs Therefore for the system to be in Automatic and manual mode all Mode inputs must be inactive Indication of the Mode is given on the front of the status unit by the Manual only or Automatic an...

Page 9: ...e located along the bottom of the PCB and are as follows 4 8 1 COM This LED indicates that the data communications connection to the control panel is not present This may be because the data lines are...

Page 10: ...ERED DOWN BEFORE ANY CHANGES TO DEVICES IMPORTANT Devices with the same address will cause an intermittent fault to be displayed Assigning Sign Function In addition to addressing signs connected to th...

Page 11: ...utton on the module to view the faults If status units are detected the LCD will display X the address of the status unit found To accept the status units found slide the WRITE ENABLE switch on the mo...

Page 12: ...p to 3 additional signs There is no need to configure the address or sign function switches however the internal buzzer and flashing functions can still be adjusted separately IMPORTANT An additional...

Page 13: ...cables for the RS485 circuit with the FIP effectively in the middle of the circuit rather than at one end FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If process is done with power connected...

Page 14: ...ame as another device in the 485 circuit Power has failed to the LCS RS485 signal has failed to the LCS 9 Specifications Internal Sign External Sign Local Control Station Size 195 x 300 x 50mm 195 x 3...

Reviews: