background image

Sigma_XT_signs_m3.5.docx 

 

     

Page 9 of 14

 

 

Processor and Watchdog Reset Switches 

The status unit is controlled by a microprocessor, which will re-start 
itself  and  continue  to  run  if  it  stops  for  any  reason  such  as  severe 
electrical interference such as an electrical storm.  
To  ensure  that  the  unit  is  not  being  subjected  to  continual,  undue 
interference  which  may  affect  its  proper  operation,  a  CPU  fault 

indicator  is  latched  on  and  a  fault  condition  signalled  to  the  control 
panel.  
If  a  processor  re-start  has  occurred  this  latched  fault  condition  will 
need to be reset by pressing the WDOG RESET button on the bottom 
of the PCB. 
A  switch  is  also  provided  to  manually  re-start  the  processor  PROC 
RESET. This switch can be used while the status units are connected 

to  the  system  to  ensure  that  the  unit  starts  up  and  establishes 
communication with the panel in a controlled and expected manner.  

 

Internal fault indications 

An extinguishant fault indication at the control panel may mean that there are faults at one or more status 
units. The status unit fault indications are located along the bottom of the PCB and are as follows: 

4.8.1.

 

COM 

This  LED  indicates  that  the  data  communications  connection  to  the  control  panel  is  not  present.  This  may  be 

because  the  data  lines  are  connected  with  reverse  polarity  or  are  not  connected.  Check  RS485  IN  and  OUT 
connections. 

4.8.2.

 

LOCK OFF 

This LED indicates that the Lock Off input is open or short circuit. Check that the correct end of line resistor is 

connected to the Lock Off terminals or at the end of the wires connected to the Lock Off terminals and that the 
Lock Off input is not short circuited, or the wiring open circuited. 

IMPORTANT NOTE: When there is a fault on the Lock Off input then the Lock Off function is invoked which means that the 
extinguishant release will not operate until this condition is cleared. 

4.8.3.

 

MOD 

This  LED  indicates  that  the  MODE  input  is  open  or  short  circuit.  Check  that  the  correct  end  of  line  resistor  is 
connected to the MODE terminals or at the end of the wires connected to the MODE input and that the MODE input 
is not short circuited. 

4.8.4.

 

FUSE 

This LED indicates that the electronic fuse has operated. Under this condition, the status unit is not operational. 
This may be due to incorrect polarity of the power connection or a failure on the unit itself. 

 

 

 

Summary of Contents for Sigma XT

Page 1: ...Fire Alarm and System Warning Signs Local Control Stations Installation and Operations Manual Serial Communications Type SIGMA XT FP Issue 3 5 March 2020...

Page 2: ...CS 7 Power and Data Connection 7 Connection to Hold and Mode inputs 8 Mode input 8 Hold input 8 Mode select keyswitch 8 Manual release 8 Processor and Watchdog Reset Switches 9 Internal fault indicati...

Page 3: ...tatus units have monitored inputs to which remote Hold or Mode select switches can be connected These inputs are monitored for open and short circuit faults and therefore need to have a 470R 1W trigge...

Page 4: ...Signs Mount Sunshade Remove cover and Internal circuit board Mount using suitable fixings ONLY Mount to sunshade surface if the enclosure is twisted on mounting it will crack over time Best practice...

Page 5: ...he corresponding terminals at the control panel Connecting Signs with RS485 Serial 3 1 1 Connecting up to 3 Signs For systems requiring up to 3 signs or devices to be installed wiring is as follows No...

Page 6: ...WN BEFORE ANY CHANGES TO SIGNS Connections for the first 3 signs or devices remains the same as the previous wiring diagram For more than 3 signs a separate power supply is required from the 24VDC out...

Page 7: ...r systems requiring a LCS to be installed wiring is as follows Notes FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If installed as one of the first 3 devices on the STATUS SERIAL RS485 circuit...

Page 8: ...e inputs Therefore for the system to be in Automatic and manual mode all Mode inputs must be inactive Indication of the Mode is given on the front of the status unit by the Manual only or Automatic an...

Page 9: ...e located along the bottom of the PCB and are as follows 4 8 1 COM This LED indicates that the data communications connection to the control panel is not present This may be because the data lines are...

Page 10: ...ERED DOWN BEFORE ANY CHANGES TO DEVICES IMPORTANT Devices with the same address will cause an intermittent fault to be displayed Assigning Sign Function In addition to addressing signs connected to th...

Page 11: ...utton on the module to view the faults If status units are detected the LCD will display X the address of the status unit found To accept the status units found slide the WRITE ENABLE switch on the mo...

Page 12: ...p to 3 additional signs There is no need to configure the address or sign function switches however the internal buzzer and flashing functions can still be adjusted separately IMPORTANT An additional...

Page 13: ...cables for the RS485 circuit with the FIP effectively in the middle of the circuit rather than at one end FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If process is done with power connected...

Page 14: ...ame as another device in the 485 circuit Power has failed to the LCS RS485 signal has failed to the LCS 9 Specifications Internal Sign External Sign Local Control Station Size 195 x 300 x 50mm 195 x 3...

Reviews: