background image

Sigma_XT_signs_m3.5.docx 

 

     

Page 8 of 14

 

 

Connection to Hold and Mode inputs 

Status units have monitored inputs to which remote Hold or Mode select switches can be connected.  These inputs 
are monitored for open and short circuit faults and therefore need to have a 470R 1W trigger resistor connected in 

series with the activating, normally open switches and 6K8 0.5W end of line monitoring resistors connected across 
the end of the cables. 
The 6K8 end-of-line monitoring resistors are supplied fitted to the Hold and Mode input terminals and the 470R 

trigger resistors are supplied in the accessory bag with the status unit.  If either of these inputs are not being used 
then the end of line monitoring resistors should be left in the Hold and/or Mode terminals. 

 

 

Mode input  

The mode input is provided to allow connection of remote mode switch or to connect to door interlock contacts.  

The system is designed such that any Manual only mode input on the system that is active (input operated by 470R 
trigger  resistor)  will put  the system into Manual only mode regardless of the status of any other Mode inputs.  
Therefore, for the system to be in Automatic and manual mode, all Mode inputs must be inactive.  
Indication of the Mode is given on the front of the status unit by the Manual only or Automatic and manual LEDs.  

 

Hold input  

When active (input operated by a 470R trigger resistor) the Hold input allows the extinguishant release countdown 
timer to be reset to its maximum time.  When the input is de-activated the countdown to extinguishant release will 
re-start at the maximum time that is configured at the panel (0 to 60 seconds). 

IMPORTANT NOTE: When there is a fault on the HOLD input then the HOLD function is invoked which 
means that the extinguishant release will not operate until this condition is cleared. 

 

Mode select keyswitch  

Some models of the status units have a mode select switch.  The operation of the Mode select switch is as per the 
Mode input above.  

 

Manual release  

Where fitted, a manual release button replicates the action of the manual release control at the main control panel 
and once activated will start the extinguishant release sequence.  
A plastic seal is provided in the accessory pack and should be fitted to the manual release flap with a piece of thin 
wire to provide an indication if the manual release has been tampered with. 
3 Processor and watchdog reset switches  

Summary of Contents for Sigma XT

Page 1: ...Fire Alarm and System Warning Signs Local Control Stations Installation and Operations Manual Serial Communications Type SIGMA XT FP Issue 3 5 March 2020...

Page 2: ...CS 7 Power and Data Connection 7 Connection to Hold and Mode inputs 8 Mode input 8 Hold input 8 Mode select keyswitch 8 Manual release 8 Processor and Watchdog Reset Switches 9 Internal fault indicati...

Page 3: ...tatus units have monitored inputs to which remote Hold or Mode select switches can be connected These inputs are monitored for open and short circuit faults and therefore need to have a 470R 1W trigge...

Page 4: ...Signs Mount Sunshade Remove cover and Internal circuit board Mount using suitable fixings ONLY Mount to sunshade surface if the enclosure is twisted on mounting it will crack over time Best practice...

Page 5: ...he corresponding terminals at the control panel Connecting Signs with RS485 Serial 3 1 1 Connecting up to 3 Signs For systems requiring up to 3 signs or devices to be installed wiring is as follows No...

Page 6: ...WN BEFORE ANY CHANGES TO SIGNS Connections for the first 3 signs or devices remains the same as the previous wiring diagram For more than 3 signs a separate power supply is required from the 24VDC out...

Page 7: ...r systems requiring a LCS to be installed wiring is as follows Notes FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If installed as one of the first 3 devices on the STATUS SERIAL RS485 circuit...

Page 8: ...e inputs Therefore for the system to be in Automatic and manual mode all Mode inputs must be inactive Indication of the Mode is given on the front of the status unit by the Manual only or Automatic an...

Page 9: ...e located along the bottom of the PCB and are as follows 4 8 1 COM This LED indicates that the data communications connection to the control panel is not present This may be because the data lines are...

Page 10: ...ERED DOWN BEFORE ANY CHANGES TO DEVICES IMPORTANT Devices with the same address will cause an intermittent fault to be displayed Assigning Sign Function In addition to addressing signs connected to th...

Page 11: ...utton on the module to view the faults If status units are detected the LCD will display X the address of the status unit found To accept the status units found slide the WRITE ENABLE switch on the mo...

Page 12: ...p to 3 additional signs There is no need to configure the address or sign function switches however the internal buzzer and flashing functions can still be adjusted separately IMPORTANT An additional...

Page 13: ...cables for the RS485 circuit with the FIP effectively in the middle of the circuit rather than at one end FIP MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS If process is done with power connected...

Page 14: ...ame as another device in the 485 circuit Power has failed to the LCS RS485 signal has failed to the LCS 9 Specifications Internal Sign External Sign Local Control Station Size 195 x 300 x 50mm 195 x 3...

Reviews: