www.desatech.com
114745-01D
8
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12"
of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation
for
required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic
will activate the power vent.
AIR FOR COMbUSTION
AND VENTILATION
Continued
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside
Building
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary
heating source. If you have a
central heating system, you may
run system's circulating blower
while using heater. This will help
circulate the heat throughout the
house. In event of a power out-
age, you can use this heater as
your primary heat source.
WARNING: A qualified ser-
vice person must install heater.
Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appli-
ance in a vented configuration.
Check your state or local codes.
WARNING: Make sure the
selector switch is in the OFF po-
sition before installing heater.
WARNING: Before installing
in a solid fuel burning fireplace,
the chimney flue and firebox
must be cleaned of soot, creo-
sote, ashes and loose paint by a
qualified chimney cleaner. Creo-
sote will ignite if highly heated. A
dirty chimney flue may create and
distribute soot within the house.
Inspect chimney flue for damage.
If damaged, repair flue damper
before operating appliance.