PRODUCT OVERVIEW

PRODUCT APPLICATION:
The Firex Series Duct Smoke Detectors provide early detection of smoke and products of combustion present in air moving through an HVAC
duct in commercial, industrial and residential applications.

These devices are designed to prevent the recirculation of smoke in areas by the air handling systems, fans and blowers.  Complete systems
may be shut down in the event of smoke detection.

NOTE
For the correct installation of a duct smoke unit, please refer to the NFPA 72E (Standard for Automatic Fire Detectors), NFPA 90A (Standard for
Installation of Air Condition and Ventilation Systems) and NFPA 92A (Recommended practice for smoke control systems.)

This detector is not intended for open area protection nor should it be used for early warning detection or replace a regular fire detection system.

Maple chase provides a special U.L. 50 listed, NEMA 3R rated weatherproof enclosure separately (Model 0590) which should be used in
appropriate outdoor applications for protection from the elements.  Other installations above the roof line (attics, banjo type roofs, etc.) do not
require our special Model 0590 weatherproof enclosure as long as the Maple Chase duct smoke detectors are not exposed to dripping water or
other environmental  elements.  Our Model 0590 weatherproof enclosure should be used in all applications where environmental elements are
a concern or local code requires a weatherproof enclosure for proper installation.  All installations of our duct smoke detectors and weatherproof
enclosures should be done in accordance with all applicable electrical and building codes.

PRODUCT DESCRIPTION:  
The Firex Smoke Detector is fitted with a mounting base that will accept an Apollo Ionization Model # 55000 - 250 or Photoelectric Detector
Head Model # 55000 - 350.  The duct unit supports 2 sets of Form “C” Alarm Contacts and 1 form “C” Trouble Contact. The trouble contact
supervises the presence of the input power and removal of the detector head. 

THE TROUBLE CONTACTS (TERMINALS 13-14-15) ARE SHOWN IN THE NON-ENERGIZED CONDITION.

The trouble contact will not operate in the event of a smoke alarm.

The Firex Duct Detector models 2650-560 and 2650-561 will operate on one of the following input voltage sources: 24V.A.C., 24V.D.C., 115V.A.C
and 230V.A.C..

The duct smoke detector units are designed to operate in duct widths from 12 inches to 10 feet wide with an air velocity between 300 and 4000
feet per minute.  To verify correct installation, the pressure differential between the input and exhaust tubes should be 
measured using a Magnehelic pressure gauge or equivalent.  An acceptable reading must be between 0.01 and 1.2 inches of water.

For a Smoke Duct Detector unit to operate correctly, it must be installed 6 duct widths from any obstruction i.e. elbows, deflector plates, filters,
dampers, etc.  In situations where the criteria cannot be met, deviations are acceptable providing they meet the pressure differential
requirements.

SAMPLING TUBES:
The principal of operation of a duct detector is based on the Venturi effect.  Two tubes extend into the HVAC duct.  Air flowing through the duct
is forced into the air intake tube via the air intake holes, and passes over the detector head.  The air will be drawn out via the exhaust tube back
into the HVAC duct.  (7” exhaust tube provided in the installation kit.)

When the particles of smoke suspended in the air stream reach the alarm threshold of the detector head, the unit will go into alarm.

REMOTE ACCESSORIES:
Audible and visual alarm indicators, remote status indicators and remote reset/test switches can be accommodated by the 
Firex Duct units by connecting to the D.C. voltage output terminals 16 to 20 (see page 6 for details).  These terminals are not supervised and
the current will only be present when the detector unit is in alarm.  The remote pilot led will be permanently illuminated when connected to the
output terminals.

MODEL 2650-560 Ionization
MODEL 2650-561 Photoelectric

INSTALLATION INSTRUCTIONS FOR

UNIVERSAL DUCT SMOKE DETECTORS

1

Summary of Contents for 2650-560

Page 1: ...s the presence of the input power and removal of the detector head THE TROUBLE CONTACTS TERMINALS 13 14 15 ARE SHOWN IN THE NON ENERGIZED CONDITION The trouble contact will not operate in the event of a smoke alarm The Firex Duct Detector models 2650 560 and 2650 561 will operate on one of the following input voltage sources 24V A C 24V D C 115V A C and 230V A C The duct smoke detector units are d...

Page 2: ...de air 5 When installing duct smoke units down stream of filters fires occurring in the filters will be detected but if the filters become blocked insufficient air flow through the duct unit will prevent the correct operation of the duct detector 6 Where possible install duct detectors upstream of air humidifies and downstream of dehumidifiers 7 To prevent false alarms the duct detector should not...

Page 3: ... pressure between the inlet and exhaust tubes The differential pressure between the two tubes should be greater than 0 01 inches of water and less than 1 2 inches of water Model Number Apollo Detector Model Number S60A Ionization Detector 55000 250 S60A Photoelectric Detector 55000 350 POWER REQUIREMENTS QUIESCENT CURRENT ALARM CURRENT 24V AC 35 mA 24V AC 74mA 24V DC 15 mA 24V DC 48mA QUIESCENT CU...

Page 4: ... inches for 2 seconds CAUTION SPRAYING FROM A DISTANCE CLOSER THAN 12 INCHES CAN CAUSE DETECTOR CONTAMINATION After 15 to 20 seconds the detector head will go into alarm illuminating the detector head led and causing the duct unit functions to operate relays will change state and the remote accessories if attached will function If no test gas is available to conduct the testing light a piece of cl...

Page 5: ... will be energized The green led will be illuminated When pressing the test reset button the red Alarm led will be illuminated In the event of a fire alarm certain equipment may have to be shut down A shut down will be achieved by interrupting the supply source to that particular piece of equipment when wired as indicated below EXAMPLE Fan Supply Source 7 9 NC C NO RELAY P P 1 Dedicated INPUT Volt...

Page 6: ...the detector head in alarm will be illuminated all other head leds will be off With multiple units connected a common reset will be achieved by interrupting the supply voltage REMOTE ACCESSORY WIRING Remote accessory terminals 16 to 20 are not supervised and the output voltage will be present when the duct detector is in alarm or the test reset switch is operated For the 0543 0544 accessories with...

Reviews: