background image

MAGNET TESTING:

Place the magnet provided with the instruction kit on top of the housing between the raised sections above the detector

head (as indicated on the unit cover). Allow at least five (5) seconds for alarm initiation. Remove magnet and reset detector.

SMOKE TESTING:

Using smoke test canister with testing nozzle (Part Number 565), insert the test gas nozzle into the test point on the unit

cover. Press can against cover to release gas into chamber. CAUTION: Do not spray gas for more than 1/2 second. Overuse of test gas
facility will result in detector contamination.

After 15 to 20 seconds the detector head will go into alarm, illuminating the detector head LED and causing the duct unit functions to operate,
relays will change state and the remote accessories if attached will function. Please allow several minutes for the gas to evaluate the chamber
before the detector may be reset.

If no test gas is available to conduct the testing, remove cover and blow smoke from a cotton wick or punk directly at the head to cause alarm.
The alarm indicator will illuminate within one minute. 

Should testing be required for simulated fire conditions, smoke bombs placed in the duct may not be suited for the particular detector head
selected and installed.

Ionization Detector Head 2850-450 utilizes a radioactive source as its means of detection and will detect smoke particles of between .1 and 1
micron in size.

Photoelectric Detector Head 2850-550 operates on the principle of light scatter and will detect smoke particles of between 1 and 10 microns in
size.

When purchasing smoke bombs for functional testing, ensure smoke particle sizes comply with the criteria as described above.

MAINTENANCE

Each installation location must be assessed on its own merits.  If the protected area is of a very dirty nature then the Firex Duct units will have
to be checked and cleaned on a Quarterly basis or when cleaning is required.

As a guideline the detector head should be cleaned every six months or as required.

The best methods of cleaning are to vacuum the detector head thoroughly or to blow the detector head out using compressed air.

Do not use chemicals to clean the detector head housing as this could contaminate the detector head and damage the casing.

Sensing tubes must be inspected and cleaned in accordance with the schedule as determined above, to allow the free flow of air through the
sensing tube.

AP 186   MA 2650-760; 01/01

Model Number:

Detector Model Number:

S65 Ionization Detector Head  2850-450
S65 Photoelectric Detector Head    2850-550

POWER REQUIREMENTS

QUIESCENT CURRENT

ALARM CURRENT

24V  AC   39.4mA 24V  AC   128.7mA
24V  DC   13.5mA 24V  DC     59.3mA

115V AC   13.8mA 115V AC     27.0mA

230V AC     7.9mA 230V AC     16.0mA

RELAY CONTACT RATINGS:

Alarm contacts: 2 form “C” rated at 10AMPS @ 115V AC resistive, 1 Form A @ 2AMPS
Trouble contacts: 1 Set form “C” rated at 10AMPS @ 115V AC resistive
Air velocity: 300 to 4,000 ft/min
Ambient temperature: Model 2650-760   32

o

F to 1

55

o

F (0

o

C to 

6

8

o

C)

:

Model 2650-761   32

o

F to 100

o

F (0

o

C to 38

o

C)

Humidity:  

10% to 85% R.H. no condensation

Material:

Gray plastic backbox with clear plastic cover

Dimensions:

L-13 1/2”, X H-4 1/2”, Depth - 2 1/4”

Max. net wt.:

3 lbs.

Radioactive element:

For Firex 2650-760 (Ionization model)
Americium 241, 0.9 micro curie

Do not expose to corrosive atmospheres.

PRODUCT SPECIFICATIONS

2650-760 Ionization

24V AC/DC, 115V AC, 230V AC

2650-761 Photoelectric

24V AC/DC, 115V AC, 230V AC

Maple Chase Company

2820 Thatcher Road
Downers Grove, Illinois 60515 USA
Tel1 630 719 5500  Fac1 630 719 4400
Technical Service Tel1 800 445 8299
E-mail mctechservices@maplechase.com
www.maplechase.com

TM

Summary of Contents for 2650-760

Page 1: ...2650 760 and 2650 761 will operate on one of the following input voltage sources 24VAC 24VDC 115VAC and 230VAC The duct smoke detector units are designed to operate in duct widths from 12 inches to 10 feet wide with an air velocity between 300 and 4 000 feet per minute To verify correct installation the pressure differential between the input and exhaust tubes should be measured using a Magnehelic...

Page 2: ...dths of 2 5 TO 5 0 554 For duct widths of 5 0 TO 10 0 The standard sampling tubes are steel tubes with air intake holes drilled down the entire length of the tube These tubes must be cut to length and must span the entire width of the duct Sampling tubes over 3 0 feet must be supported on the opposite side of the duct To ensure the correct operation of the sensing tube the red end cap red stopper ...

Page 3: ...trouble contacts 4 15 5 will not change state in the event of a fire alarm operational or functional testing The trouble contacts can be tested by rotating the Apollo detector head counter clockwise and removing the detector head This action will extinguish the pilot green LED and cause the trouble contacts to change state 4 15 will be closed continuity 5 15 will be open circuit Replacing the dete...

Page 4: ...on must be assessed on its own merits If the protected area is of a very dirty nature then the Firex Duct units will have to be checked and cleaned on a Quarterly basis or when cleaning is required As a guideline the detector head should be cleaned every six months or as required The best methods of cleaning are to vacuum the detector head thoroughly or to blow the detector head out using compress...

Page 5: ...TEST RESET ALARM WHEN NOT INTERCONNECTED PILOT 2 Remote Accessories Approved For Use With This Detector 535 Remote Alarm 542 Remote Alarm Pilot Horn key operated Test Reset Switch 536 Remote Alarm push button Test Reset Switch 543 Remote Alarm Pilot Horn 537 Remote Alarm Pilot push button Test Reset Switch 544 Remote Alarm Trouble Pilot Horn key operated Test Reset Switch 538 Remote Alarm key oper...

Page 6: ...ROBE OPERATE ON ALARMED DETECTOR ONLY 30 DETECTORS MAX ALL RELAYS OPERATE WITH SINGLE ALARM ALL HORN STROBES OPERATE WITH SINGLE ALARM 10 DETECTORS MAX COMMON TEST RESET 30 DETECTORS ONLY NORMALLY OPEN RESET SWITCH Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 12 12 12 H RED BLK H RED BLK H RED BLK 13 14 19 20 13 14 19 20 13 14 19 20 12 12 12 H RED BLK H RED B...

Reviews: