8
See bottom of page 12 for further details.
HEP-2-Zxxxx
- Portable high-energy hand-held ignitor with mains cable and carrying strap
HE-S / HE-L
- Ignition tip short / long (to be selected depending on the required overall length)
(Representation with optionally available grab handle HEP-2-GRIP)
The ignition unit is already pre-assembled. Only the ignition tip HE-S or HE-L has to be screwed in.
For personal protection and for later use, it is recommended to connect a protective conductor (minimum cross-sec
-
tion 4mm²) to the external PE connection bolt of the junction box with a grounding clamp for connecting the ground
potential to the burner (see installation instructions described below).
Protective conductor assembly
The insulation of the PE wire must be offset by approx. 8mm at the end. The supplied yellow ring cable lug
(4 mm²) is fitted here with crimping pliers (model for insulated ferrules with forced lock). The yellow ferrule is placed
on the external grounding bolt on the housing and secured with the washer and serrated lock washer and a nut.
On the other side of the PE cable, a grounding clamp should be connected to metal surfaces grounded on the system
side for easy handling to ensure good contact.
A ready-made PE cable with mounted grounding clip is available as an accessory (HEP-2-CLIP).
INDIVIDUAL COMPONENTS HEP-2-Zxxx WITH FIXED IGNITION ELECTRODE
HE-L
HE-S
HEP-GRIP (Optional)
HEP--Zxxxx