© 2020 Carrier
16
Scanner Cable with Female Connector, 59-547-x
Fireye offers 59-547 (12-conductor) cables in precut lengths with a female factory installed connector.
These assemblies are offered in several lengths ranging from 3 meters (9 ft., 10 in.) to 90 meters (295
ft., 3 in.)
Table 1:
SCANNER CABLES 59-547-x
PART
NUMBER
DESCRIPTION
LENGTH
METERS
FEET
59-547-3
12-Conductor 3-meter cable assembly with 12-pin female connector.
3 meters
9 feet, 10 inches
59-547-6
12-Conductor 6-meter cable assembly with 12-pin female connector.
6 meters
19 feet, 8 inches
59-547-9
12-Conductor 9-meter cable assembly with 12-pin female connector.
9 meters
29 feet, 3 inches
59-547-12
12-Conductor 12-meter cable assembly with 12-pin female connector.
12 meters
39 feet, 4 inches
59-547-15
12-Conductor 15-meter cable assembly with 12-pin female connector.
15 meters
49 feet, 2 inches
59-547-30
12-Conductor 30-meter cable assembly with 12-pin female connector.
30 meters
98 feet, 5 inches
59-547-45
12-Conductor 45-meter cable assembly with 12-pin female connector.
45 meters
147 feet, 7 inches
59-547-60
12-Conductor 60-meter cable assembly with 12-pin female connector.
60 meters
196 feet, 10 inches
59-547-90
12-Conductor 90-meter cable assembly with 12-pin female connector.
90 meters
295 feet, 3 inches
59-547
12-Conductor cable
without connector
. Sold by the foot for use as extension
cable from a junction box.
-
As required
SCANNER WIRING
To reduce electrical noise interference, take precautions to keep the scanner cable away from any high
inductive wiring associated with high inductive loads or high voltage, high energy spark ignition sys-
tems.
CAUTION: The flame scanner requires 24 Vdc power for operation. Connection to a 24 Vac
or 120/230 Vac power source will damage the scanner. Refer to wiring diagrams.
External 0.5 Amp slow-blow fuses are recommended to protect Flame Relay and Fault Relay
contacts
All wiring to the scanner must be rated at 105°C. For runs less than 1000 feet, the use of Fireye
Scanner Cable P/N 59-547, (12 wire) is recommended. For runs in excess of 1000 feet, consult
the factory.
Summary of Contents for InSight 4 Series
Page 19: ... 2020 Carrier 19 Figure 14 WIRING DIAGRAM 95UVS4 1 95IRS4 1 with 59 547 cable ...
Page 27: ... 2020 Carrier 27 THE MAIN STATUS MENU FIGURE 20 MAIN STATUS MENU LOOP ...
Page 36: ... 2020 Carrier 36 THE CONFIG MENU FIGURE 23 CONFIG MENU LOOP ...
Page 40: ... 2020 Carrier 40 THE AUTO CONFIG MENU FIGURE 25 AUTO CONFIG MENU LOOP ...
Page 43: ... 2020 Carrier 43 THE FILE COPY MENU FIGURE 26 FILE COPY MENU LOOP ...
Page 45: ... 2020 Carrier 45 THE 4 20 mA MENU FIGURE 27 4 20mA MENU LOOP ...
Page 47: ... 2020 Carrier 47 THE DATE TIME MENU FIGURE 28 DATE TIME MENU LOOP ...
Page 49: ... 2020 Carrier 49 THE COMMS MENU FIGURE 29 COMMS MENU ...
Page 51: ... 2020 Carrier 51 THE MANUAL CONFIG MENUS FIGURE 30 ...
Page 52: ... 2020 Carrier 52 MANUAL CONFIG MENUS continued FIGURE 31 ...