Internal Error Messages
DISPLAYED WHEN ERROR OCCURS
DISPLAYED LATER IN ERROR HISTORY MENU
INTERNAL STORAGE R/W ERROR
FRAM WRITE FAIL
INTERNAL STORAGE R/W ERROR
FRAM READ FAIL
WATCH DOG FAILURE
WATCH DOG FAIL
INTERNAL RAM CHECK FAILURE
RAM TEST FAIL
INTERNAL RAM CHECK FAILURE
BI RAM TEST FAIL
INTERNAL VOLTAGE CHECK FAILURE
VOLTAGE TEST
RELAY FEEDBACK CHECK FAILURE
RELAY FB CHECK
INTERNAL CPU1 INIT FAILURE
FAILED INIT
INTERNAL STORAGE MEMORY CORRUPTED
INVALID FRAM
INTERNAL STORAGE MEMORY CORRUPTED
WRONG FRAM REV
INTERNAL CPU2 STATUS FAILURE
CPU2 STATUS FAIL
INTERNAL CPU1 CRC FAILURE
CRC ERROR
CONFIGURATION CHECK FAILED
CONFIG ERROR
CPU1 SELF CHECK FAILED TEST # xx
SELF CHECK ERROR
GENERAL FIRMWARE CHECK FAILED
GENERAL ERROR
LOCKOUT UNDEFINED ERROR
UNKNOWN REASON
Warning Messages
In the event of an abnormal operating condition the scanner will automatically display a warning
message informing the user of the condition. The warning message will be displayed for two (2)
seconds, then the standard status message will be displayed for ten (10) seconds. This pattern will be
repeated until the abnormal condition no longer exists, or until the user depresses any key. If the user
depresses any key, the warning message will be suppressed for thirty (30) seconds.
Group I Warning Messages (Always Active
)
Warning Message
Condition
Effect
TOO COLD < -40C
Currently –xxC
FLAME SIGNAL SET TO 0
The scanner’s internal temperature has fallen to -40C (-
40F), or below. Note: There is a 2°C hysteresis window (-
38°C) until cold warning displayed.
Flame signal is driven to zero. The Flame and
Fault relays will be de-energized.
COLD WARNING
Currently –xxC
The scanner’s internal temperature has fallen to -35C (-31F)
or below
The Fault relay will be de-energized.
HOT WARNING
CurxxC
The scanner’s internal temperature has risen to +80C
(+176F), or higher
The Fault relay will be de-energized.
TOO HOT > 85C
CurxxC
FLAME SIGNAL
SET TO 0
The scanner’s internal temperature has risen to +85C
(+185F), or higher. Note: There is a 2°C hysteresis window
(83°C) until hot warning displayed.
Flame signal is driven to zero. The Flame and
Fault relays will be de-energized
IR SENSOR IS SATURATED
The steady (DC) component of the IR source is too strong
(the flame is too bright). The scanner cannot properly detect
the flame flicker. (See note 3).
The IR flame signal will become
erratic or go to zero.
Summary of Contents for InSight 4 Series
Page 19: ... 2020 Carrier 19 Figure 14 WIRING DIAGRAM 95UVS4 1 95IRS4 1 with 59 547 cable ...
Page 27: ... 2020 Carrier 27 THE MAIN STATUS MENU FIGURE 20 MAIN STATUS MENU LOOP ...
Page 36: ... 2020 Carrier 36 THE CONFIG MENU FIGURE 23 CONFIG MENU LOOP ...
Page 40: ... 2020 Carrier 40 THE AUTO CONFIG MENU FIGURE 25 AUTO CONFIG MENU LOOP ...
Page 43: ... 2020 Carrier 43 THE FILE COPY MENU FIGURE 26 FILE COPY MENU LOOP ...
Page 45: ... 2020 Carrier 45 THE 4 20 mA MENU FIGURE 27 4 20mA MENU LOOP ...
Page 47: ... 2020 Carrier 47 THE DATE TIME MENU FIGURE 28 DATE TIME MENU LOOP ...
Page 49: ... 2020 Carrier 49 THE COMMS MENU FIGURE 29 COMMS MENU ...
Page 51: ... 2020 Carrier 51 THE MANUAL CONFIG MENUS FIGURE 30 ...
Page 52: ... 2020 Carrier 52 MANUAL CONFIG MENUS continued FIGURE 31 ...