THE COMMS MENU
MODBUS ADDRESS
This option allows the user to select the device modbus address. (Affects all files)
The communications address selected may range from 001 to 247. Each scanner must have a unique
address. No two scanners in a communications loop can have the same address. Default factory
address for InSight Series 4 is 247.
MODBUS BAUD
This option allows the user to set modbus communication baud rate. Valid values are 4800, 9600,
19200 and the factory default baud rate is 19200
MODBUS PARITY
This option allows the user to set communication parity. Valid values are 8/N/1, 8/E/1, 8/N/2, 8/O/1.
Default factory parity is 8/N/1.