SPECIFICATIONS
MECHANICAL:
Housing Material:
Standard Models and CEX: Cast aluminum with gray polyester powder coat finish
Ingress Protection IP66 with 0.4 joule impact rating
Housing Weight:
Standard Models: 5.0 lbs. (2.3kg); CEX Model: 6.3 lbs. (2.9kg)
Mounting:
Requires one threaded mounting flange, ordered separately (see below).
For fiber optic mount, refer to bulletin CU-117. In the specific case of installation on InSight
I fiber optics already in place refer to bulletin 133-754 and use Adapter Kit 129-193.
Cooling / Purge Air Requirements
:
Source:
Clean, dry, cool
Volume:
4 SCFM (113 l/min) at 3/8” threaded mounting flange, or 1 inch “Y” fitting,
mounted on scanner sight pipe. Temperature near the upper limit of the scanner
operating range and/or use with dirty/dusty fuels may require up to 15 SCFM (425
l/min).
Pressure:
Adequate to overcome furnace or windbox pressure
Operating Temperature Rating:
-40°F to +150°F (-40°C to +65°C) ambient; -40°F to 176°F (-40°C to 80°C),
scanner internal temperature.
Storage Temperature Rating:
-40°F to + 185°F Ta (-40°C to +85°C Ta)
Humidity:
0% to 95% relative humidity, non-condensing
STANDARD MOUNTING FLANGE:
Material:
Cast aluminum with gray polyester powder coat finish. Contains an
integral
heat-insulating female thread insert
Flange Threads:
P/N 60-2919-1 1" NPT female pipe mount with 3/8” NPT female cooling air connection.
P/N 60-2919-2 1" BSP female pipe mount with 3/8” BSP female cooling air connection.
OPTIONAL MOUNTING FLANGE, CAST ALUMINUM:
Material:
Cast aluminum (without heat-insulating thread insert), with grey polyester powder coat
finish
Flange Threads:
P/N 60-2692, 1" NPT female pipe mount with 3/8" NPT female cooling air connection.
P/N 60-2693, 1" BSP female pipe mount with 3/8" BSP female cooling air connection.
ELECTRICAL:
Input Power:
24 Vdc, +10%, -15% supply current: 0.25A, 6VA, Hold Time must be 20 msec
Min. Fireye power supply 60-2685 is recommended
Electrical Connection:
12-pin screw type quick-disconnect
Relay Output:
FLAME RELAY, - 1 : SPST (N.O.) / -2:SPDT (Form-C)
FAULT RELAY, SPST (N.C.)
Contact Rating:
Minimum: 10 mA @ 5 Vdc (All models)
Maximum: 2 A @ 30 Vdc; 2A @ 50 Vac (Series 4E-1WINC models only)
Maximum 2A @ 30 Vdc; 2A @ 230 VAC (All other models)
Analog Output:
4-20 mA dc current, referenced to 24Vdc common, Max. connected 1oad: 750 ohms
Operator Interface:
Alpha -Numeric Display with five pushbutton keys.
Cable Specification:
P/N 59-547 (12-conductor):
Multi-core, 12 conductor (color coded), 18- AWG, with foil wrap and overall braided shield
and drain wire. PLTC-ER rating. Maximum cable length 1000 feet (305 meters) Cable
Jacket: PVC / black (flame-retardant, RoHS compliant)
Temperature Rating: -40°F to +221°F (-40°C to +105°C)
Nominal O.D. 0.52" (13.2 mm), maximum O.D. 0.56” (14.2mm)
P/N 59-497 (12 Conductor)
Multi-core, 12 conductor (color coded), with foil wrap and overall braided shield Six #18
AWG and four #22 AWG conductors, plus one #22 AWG twisted pair Cable Jacket:
Irradiated Modified Polyolefin (flame-retardant, low smoke, zero halogen) Maximum
Summary of Contents for InSight 4 Series
Page 19: ... 2020 Carrier 19 Figure 14 WIRING DIAGRAM 95UVS4 1 95IRS4 1 with 59 547 cable ...
Page 27: ... 2020 Carrier 27 THE MAIN STATUS MENU FIGURE 20 MAIN STATUS MENU LOOP ...
Page 36: ... 2020 Carrier 36 THE CONFIG MENU FIGURE 23 CONFIG MENU LOOP ...
Page 40: ... 2020 Carrier 40 THE AUTO CONFIG MENU FIGURE 25 AUTO CONFIG MENU LOOP ...
Page 43: ... 2020 Carrier 43 THE FILE COPY MENU FIGURE 26 FILE COPY MENU LOOP ...
Page 45: ... 2020 Carrier 45 THE 4 20 mA MENU FIGURE 27 4 20mA MENU LOOP ...
Page 47: ... 2020 Carrier 47 THE DATE TIME MENU FIGURE 28 DATE TIME MENU LOOP ...
Page 49: ... 2020 Carrier 49 THE COMMS MENU FIGURE 29 COMMS MENU ...
Page 51: ... 2020 Carrier 51 THE MANUAL CONFIG MENUS FIGURE 30 ...
Page 52: ... 2020 Carrier 52 MANUAL CONFIG MENUS continued FIGURE 31 ...