background image

®

 

7

 

 

 

 

 

 

8.  PILOT  START-UP, OPERATIONAL TESTS

 

Before proceeding with the start-up and operational tests of SP-48-

NG/PG-

FD pilot check the following: 

8.1  Gas  and  air  installations  are  correctly  mounted,  tight  and  functionally  checked,  including:  valves,  flaps, 

strainers, fittings and joints (flanged and screwed), control and interlock devices.

 

8.2  Gas and air connections to the pilot are made in accordance with the above instructions and the assy drawing.

 

8.3  Electrical components and circuit

s

 are properly connected, grounded and tested. 

8.4  Power  supply to  the electrical circuit of the ignition device and spark or arc release should be allowed only 

after assembly of the device, and when installed in the operating position on the burner or outside the burner 
only to validate the operation strictly according to the device instructions e.g. on special test stand.

 

Then perform next steps:

 

8.5  Select one pilot as a representative for tests.

 

8.6  Prepare the burner control system to enable manual trials in a safe way.

 

8.7  Install for the trial period appropriate gauge and manual valve on the igniter gas supply line.

 

This will allow 

for fine adjustment of the gas pressure.

 

8.8  After verification of ignition device mounting and wiring, the electric igniter can be powered up.  

Check for the spark or arc presence.

 

8.9  At  presence  of  a  spark  or  an  electric  arc  from  ignition  device,  slowly  open  the  pilot  manual  shut-off  gas 

valve  without opening the  air  manual shut-off 

valve (it should be closed). At  certain degree of  opening the 

pilot flame should establish. 

8.10  Adjust the gas pressure slowly up to the working pressure. Pilot flame may be yellow and bushy due to too 

little combustion air. 

8.11  Slowly  open  the  air  valve  manually  until  the  flame  stabilizes  at  the  end  of  the  air  tube  and  reaches  

a blue-yellow color. If the airflow is too low the end of the air tube may start to glow (it starts to glow at 400-
500

°C)

 as the main flame burns inside the igniter. Further opening of the air valve should stabilize the flame 

outside the air tube. This will stop the overheating of the air tube. Flame should be as stable as possible. 

Remarks:

:    `  

a)   Pilot  flame  should  be  blue  near the  igniter tip  and  yellow  at  its  end.  With  some  kind  of  gases  the 

flame color may stay yellow. 

b)  In some applications e.g. on up-fired burners, when the draught of the furnace is significant, it may 

be necessary to limit the amount of air by closing the air valve accordingly in order to keep stable 
pilot flame. 

c)   Gas pilot cannot be used as a burner – it works usually with preset, constant air/fuel ratio (turn-down 

ratio  1:1),  after  proper  adjustment  as  above.  However  it  should  ignite  repetitively  and  burn  with  a 
stable flame in each 

gas p

ressure point throughout the whole range after proper adjustments.

 

8.12  In  case of  insufficient pilot capacity, the amount of  gas  and air can be further adjusted bearing  in  mind the 

above principles.

 

8.13  In  multiple burner  and  pilot  applications on  one  heater/boiler with  a  similar  gas  and air  supply installation 

and similar layout on the main burner, set the other pilots gas and air valves to be in the same position.

 

8.14  Then carry out light-off tests. In case of differences in the quality of combustion adjust manual valves so that 

the flame is similar to that on the test pilot. In some cases the main burner air should be adjusted.

 

8.15  Repeat the light-off tests several times on each pilot to confirm the repeatability of ignition. Flame should be 

stable, in proper position and of desired shape.

 

If the 

SP-48-

NG/PG-

FD 

gas pilot has been correctly commissioned and the settings were optimized, with correct 

maintenance, the igniter will operate trouble free. 

 

 

 

Summary of Contents for SureFire II SP-48-NG-FD

Page 1: ...d each unit is checked and tested before dispatch Acquaintance with the following instructions and strict attention to the indications reduce the possibility of equipment failure to a minimum and ensu...

Page 2: ...xits the main nozzle at the outlet of the air tube The main flame then stabilizes in the primary combustion zone at the outlet of the air tube The swirler stabilizer plate and holes in air tube provid...

Page 3: ...he Fireye High Tension Igniter the end of the rod tip should be placed at a distance of 10 mm back from the swirler stabilizer see Fig 1 In case of the High Energy Spark Igniter the rod tip should be...

Page 4: ...ling the pilot burner please follow the rules below 6 1 Use pilot only for its intended purpose 6 2 At the time of installation operation and maintenance follow the procedures described in the instruc...

Page 5: ...he burner plate with a diameter slightly larger than the diameter of the mounting tube b The mounting tube for welding slide the mounting tube in the hole and set it in the correct position insertion...

Page 6: ...tors may be used c To ensure a long and trouble free operation of the pilot it should be kept clean Check the condition of the gas pipe and if the orifices are not blocked Remove all buildups Hoses sh...

Page 7: ...flame stabilizes at the end of the air tube and reaches a blue yellow color If the airflow is too low the end of the air tube may start to glow it starts to glow at 400 500 C as the main flame burns i...

Page 8: ...the flame after trial for ignition the valves are closed and electrical igniter is switched off i Eventual repeating of trial for ignition sequence depends on the application Details of sequence timin...

Page 9: ...does not operate correctly check the following a All manual gas valves on gas supply line were open and there is gas available b All valves in the supply line are functioning properly c The preset gas...

Page 10: ...intenance of igniter contrary to the instructions in the user manual unauthorized igniter modifications or repairs made by unauthorized personnel use of components or spare parts other than original 1...

Page 11: ...ght 3 0 m ins length The Table 2 below shows Part Numbers of gas igniter mounting tubes and spare parts Table 2 SureFire II Pilot Mounting Tubes Spare Parts Part No Description SP 48 MTF Mounting Tube...

Page 12: ...12 APPENDIX No 1 The Pilot capacity vs gas pressure graphs standard version Remark The real measured capacity may differ by 5 depending on a particular pilot and measurement conditions...

Page 13: ...us pilot on a sample main burner with gas spuds and central oil or gas gun vertical mounting The pilot air tube tip can be mounted in the throat or in the swirler Pilot tip cannot extend beyond the he...

Page 14: ...nd especially refinery gas Refinery Off Gas needs additional engineering and testing because their gas compositions and calorific values are different than these of NG PG and LPG taken for gas pilot d...

Page 15: ...5 cubic foot ft3 Air flow rate 1 cubic metre hour m3 h x 0 589 standard cubic foot min SCFM Weight 1 kilogram kg x 2 2046 pound lb Pressure 1 kilopascal kPa x 6 895 pound square inch gauge psig x 4 01...

Page 16: ...is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND...

Reviews: