Recommendation:
The set-point should be 20% higher than the first reading made, when filling the clean water
basin is filled for the first time.
The TIMER
T01
must be coded to perform this reading (see section 7.2) at 1000 s, so the reading
can be done without starting the pump; as starting the pump would contaminate the water in the
basin. Once this reading is noted, re-set the
TIMER T01
to the factory setting or according to
contractual requirements.
Partial emptying operation (if Conductivity Control is applied):
Once the SET-POINT and
TIMER T07
are exceeded (the latter establishes the time the set-
point has to be continuously exceeded), the emptying motor valve will open and the water in the
basin will be renewed, due to the filling solenoid valve staying open (the filling solenoid valve is
controlled and closes only when the maximum level is detected).
A minimum partial emptying of 100s will be performed, the motor valve will be closed and the
basin filled until the float valve cuts out. The filling solenoid valve will remain open (the closing
of the filling solenoid valve is controlled only by the maximum level detector).
If the probe has no reading (it is not in contact with the water), this means the water level has
dropped below the probe electrodes. The motor valve will close and a new partial emptying
cycle will begin, with the
TIMER T02
taking note of the minimum time between partial emptying
and
TIMER T07
of the set-point time of the conductivity being continuously exceeded.
The complete cycle of this operation is performed without the pump being shut down.
Summary of Contents for CCE2.0
Page 2: ...MANUAL for the Stages Control Panel CCE2 0 2 ...
Page 14: ...MANUAL for the Stages Control Panel CCE2 0 14 Figure 3 4 Inside cover CCE2 0 standard ...
Page 53: ...MANUAL for the Stages Control Panel CCE2 0 53 13 Declaration of conformity 13 1 D C Machine ...
Page 54: ...MANUAL for the Stages Control Panel CCE2 0 54 13 2 D C Partly completed machinery ...
Page 55: ...MANUAL for the Stages Control Panel CCE2 0 55 14 Warranty ...
Page 56: ...MANUAL for the Stages Control Panel CCE2 0 56 ...
Page 57: ...IÓN F ...
Page 58: ...IÓN ...
Page 59: ...IÓN MAN P Ev1 Mv1 P P ...
Page 60: ...F IÓN ...
Page 61: ...IÓN ...
Page 62: ...IÓN MAN P Ev1 Mv1 P P ...